Permit Number: DP15-0164
Parcel: 14026038B

Address:
5735 S TUCSON BL

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP15-0164
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2015 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: December 15, 2015
DUE DATE: December 23, 2015
SUBJECT: Tucson Airport Commerce Center
TO: Bruce Paton
LOCATION: 5735 S. Tucson Blvd
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: DP15-0164
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. A few additional comments have been made based on review of the geotechnical report. The following items need to be addressed:
1) The Geotechnical report that was provided for review for the first time with the 2nd submittal requires 5,000 psi concrete be used for concrete paving per section 4.7.2 of this report. Please update detail C on sheet 7. It is acknowledged that this detail only applies to a small stretch to be used by the trash collection servicer.
2) There is a typo in detail P on sheet 8 that refers to Juarez right-of-way. While this was not commented on during the first submittal, it should be corrected since corrections will need to be made to comply with the 5,000 psi concrete pavement requirement.
3) There is a section 4.8, corrosion potential, of the geotechnical report that indicates there is a low resistivity in the soils and that metal should be kept separated from the soil, especially in moist conditions. Please verify that the galvanization is sufficient to satisfy this separation requirement.
4) The Geotechnical report, section 4.7.1, design recommendations, has a section that mentions a pavement section for a right turn lane off of Drexel. Please provide information as to what plans set this right turn lane is being built under.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.
12/18/2015 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
Principal Planner

PROJECT: DP15-0164
Address: 5735 S Tucson Boulevard
Development Package: Multi-tenant Development

TRANSMITTAL DATE: December 18, 2015

DUE DATE: December 21, 2015

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 15, 2015.

1. FOLLOW UP TO PREVIOUS COMMENT 4 - The accessible parking symbols for the two future pad parking spaces must be drawn on the site sheets.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

PREVIOUS COMMENT 04: Per the 2012 IBC table 1106.1, when providing between 151 and 200 parking spaces six accessible parking spaces are to be provided. Per the Calculations table on the cover sheet, a note has been added that the additional accessible parking spaces will be added upon future development of the site. The accessible parking spaces must be provided on this development and may be relocated upon the development of the future phase. Revise the plan to show six (6) accessible parking spaces will be provided.
*************************************************************************************
2. FOLLOW UP TO PREVIOUS COMMENT 12 - In your response to previous comment 8 Rezoning condition 5, you stated that a subdivision plat was being processed through the City of Tucson. Include as reference on all plan sheets the subdivision case number S15-050.

PREVIOUS COMMENT 12: Additional comment may be forthcoming based on the revisions to plans or responses to the zoning comments.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package site plan and any requested documents.
12/22/2015 ANDREW CONNOR LANDSCAPE REVIEW Approved