Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP15-0110
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP15-0110
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2015 SSHIELD1 ADA REVIEW Needs Review CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: New Carousel - Reid Park Zoo
Accessibility Review - On Site Only
Development Package (1st Review)
DP15-0110

TRANSMITTAL DATE: August 14, 2015

DUE DATE: August 21, 2015

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Provide a gate width dimension for the accessible gate shown on the plan, see ADAAG section 404.2.3.

Demonstrate that the minimum maneuvering clearances are met at the accessible gate shown on the plan, see ADAAG section 404.2.4

Clarify what type of latching and closing hardware is proposed for the accessible gate shown on the plan, additional comments may be forth coming.

Demonstrate on the plan how the requirements of ADAAG sections 234.2 & 234.3 are met.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2015 EGALLET1 OUT TO CUSTOMER Completed