Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP15-0087
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/05/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/08/2015 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera Principal Planner PROJECT: DP14-0087 Address: 1801 N Stone Avenue Development Package: Food Service Use (Brother Johns BBQ Restaurant) TRANSMITTAL DATE: June 8, 2015 DUE DATE: July 1, 2015 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. This plan has been reviewed for compliance with the Development Package Standards listed in section 2-06 of the City of Tucson Administrative Manual. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC). The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az This link will take you directly to the section used for the standards review. The UDC requirements are in the Unified Development Code and can be viewed at the same web link as above 1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 15, 2015. 2-06.3.0 FORMAT REQUIREMENTS 2-06.3.1 - Each sheet shall measure 24 inches by 36 inches and include a minimum one inch margin on left side and one-half inch margin on all other sides to facilitate efficient record keeping. A larger sheet format may be used with the approval of the Planning and Development Services Department (PDSD). 2-06.3.2 - All mapped data shall be drawn at an engineering scale having no more than 50 feet to the inch. This scale is the minimum accepted to assure the plan will be legible during review and when digitized and/or reduced for record-keeping purposes. The same scale shall be used for all sheets within the set. Smaller scales (60:1 or greater) may be used for some or all of the sheets with the prior approval of PDSD when it is determined legibility and the ability to be digitized and/or reduced for archiving will not be affected. 2-06.3.3 - All lettering and text (upper or lower case), and numbering, shall be a minimum of three-thirty-seconds inches in height to assure the plan will be legible during review and when digitized and/or reduced for archiving. 2-06.3.6 - Provide a blank three-inch by five-inch block in the lower right corner of the plan adjacent to the title block on the first sheet of the development package for use by Pima County Addressing. 01. COMMENT: Provide on the cover sheet only, the address block as noted by the standard above. ****************************************************************************************** 2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet. 02. COMMENT: Revise the location map on the cover sheet as noted above. ****************************************************************************************** 2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet. 03. COMMENT: Add the north arrow and the contour interval as noted by the standard above. ****************************************************************************************** 2-06.3.10 - A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet. 04. COMMENT: Include a symbol legend on the cover sheet as noted by the standard above. ****************************************************************************************** 2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet. 05. COMMENT: The sheet index shall be indexed with the following numbering system, 1 of 9, 2 of 9, etc. The index as listed can remain but the requested numbering system must be included in the index 1 of 9 A0.0 Cover Sheet etc. ****************************************************************************************** 2-06.4.0 CONTENT REQUIREMENTS 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 06. COMMENT: The email addresses of the design professionals including the owners/developers must listed on the cover sheet. The email address for each professional and owner/developer must be listed under the text block of each person as noted above. ****************************************************************************************** 2-06.4.2 - The title block shall include the following information and be provided on each sheet: 2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat; 07. COMMENT: A brief legal description is required to be listed in the title block of all plan sheets, i.e., SW ¼ of the SW ¼ of SE ¼ of Section 38 T14 R15 (applicable description for this lot). ****************************************************************************************** 2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx). 2-06.4.5 - When the development package documents consists of more than one sheet, a sheet index (a legible drawing of the site showing the area represented on each sheet) is to be placed on the cover sheet or the second sheet. 08. COMMENT: The page number and the total number of pages must be listed on each sheet, i.e., 1 of 9, 2 of 9, 3 of 9 etc. as noted by the standards above. ****************************************************************************************** 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 09. COMMENT: This project has been assigned the PDSD Development Package case number DP15-0087. List the case number in the lower right corner of plan sheets. ****************************************************************************************** 2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information. 2-06.4.4.A - Show the subject property approximately centered within the one square mile area; 2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and, 2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled. 10. COMMENT: As noted above in comment 2, the location map is to be placed in the upper right corner of the cover sheet. The map shall be drawn at a scale of three inches equals one square mile and include the information as listed in the standards above. Also see the zoning redlines on the cover sheet. ****************************************************************************************** 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes: 2-06.4.7.A.1 - List as a general note: "Existing zoning is ____." 2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. 11. COMMENT: On the cover sheet list the existing zoning of the property as noted by the standards above. It would be best to provide Zoning Data Text Block with all the zoning information listed which includes the zoning, lot size, building size, expansion calculation, vehicle and bicycle parking etc. ****************************************************************************************** 2-06.4.7.A.8 - For development package documents provide: 2-06.4.7.A.8.a - Floor area for each building; 12. COMMENT: List the building and outdoor dining areas on the cover sheet in the zoning data text block. ****************************************************************************************** 2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and, 13. COMMENT: The site has been expanded with additional land area to the north and alley vacation. List as a note in the zoning data text block the lot area expansion. Keep in mind that the approval of this Development Package will reflect the compliance review which has been discussed in meetings with the tenants, PDSD staff and the design professional of the DP. This DP must reflect the two phases which has not been presented on this DP. The approximate building footprint must be drawn and labeled on the DP. The note on the cover sheet related to the future landscape requirement for the west parking lot must include the activity number T11CM00381 as reference. I provided copies of the previously approved plans to Mario Chavez as reference for information and are to be included as reference documentation with this DP. ****************************************************************************************** 2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met. 14. COMMENT: Include in the vehicle and bicycle parking calculations, the required number of spaces for the future Phase II development. ****************************************************************************************** 2-06.4.7.B - Drainage Notes List the following notes as appropriate: 2-06.4.7.B.1 - List the following notes on all plans/plats: "The developer, any successors and assigns, will hold the City of Tucson, its officers, employees, and agents harmless from any and all claims for damages related to the use of this development as shown hereon, now and in the future, by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall." 15. COMMENT: Add on the cover sheet as a general note the statement as noted in the standard above. ****************************************************************************************** 2-06.4.7.B.2 - If applicable, list the following notes and complete the blanks. 2-06.4.7.B.3 - List the following note on all development package documents: "Drainage will remain in its natural state and will not be altered, disturbed, or obstructed other than as shown on this site plan." 16. COMMENT: Add on the cover sheet as a general note the statement as noted in the standard above. ****************************************************************************************** 2-06.4.7.C.2 - List the following note on all development package documents: "No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Section 10-01.5.0, Sight Visibility, of the Technical Standards Manual." 17. COMMENT: Add on the cover sheet as a general note the statement as noted in the standard above. ****************************************************************************************** 2-06.4.7.C.3 - Provided the following notes as applicable: 2-06.4.7.D - Utilities Note All development package documents are to include the following note: "Any relocation or modification of existing utilities and/or public improvements necessitated by the proposed development will be at no expense to the public." 18. COMMENT: Add on the cover sheet as a general note the statement as noted in the standard above. ****************************************************************************************** 2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system. 19. COMMENT: The site boundary information must be labeled; distance and bearing must be provided. ****************************************************************************************** 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. 20. COMMENT: Add the information as noted by the standard above. ****************************************************************************************** 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 21. COMMENT: Add the information as noted above. ****************************************************************************************** 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements. 22. COMMENT: Label the information as noted by the standard above. ****************************************************************************************** 2-06.4.9.G - If the project is to be phased, provide calculations, setbacks, etc., to indicate that each phase complies with all requirements as a separate entity. Show phase lines on the drawing. Show and label any temporary improvements that may be needed to make the site function for each phase as one entity. If such temporary improvements are off the site of the phase under consideration, a temporary easement or other legal documentation to assure legal use of the property is required. Note recording information. 23. COMMENT: Add the information as noted by the standard above. ****************************************************************************************** 2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section. 24. COMMENT: Add the information as noted by the standard above. ****************************************************************************************** 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. 25. COMMENT: Add the information as noted by the standard above. ****************************************************************************************** 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 26. COMMENT: Label the widths of the PAALs on the west parking lot. ****************************************************************************************** 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 27. COMMENT: Label length, width and angle of the parking spaces on the west parking. ****************************************************************************************** 2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4. 28. COMMENT: A minimum of one 12 feet by 35 feet loading zone is required for this use. The loading zone must be dimensioned and the number loading zones required and provided must be listed in the Zoning Data text Block. ****************************************************************************************** 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 29. COMMENT: Draw, label and dimension of the required number of short and long term bicycle parking facilities for the restaurant. List the number of required and provided facilities in the Zoning Data Text Block. ****************************************************************************************** 2-06.4.9.J - If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc.) 30. COMMENT: Add the information as noted by the standard above. ****************************************************************************************** 2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown. 31. COMMENT: Label the existing and future building setbacks from the Stone Avenue and Lester Street. The building setbacks along the Stone Avenue boundary is based on the greatest of 21 feet or the height of the building wall from the back of curb location (existing and future curb location). The building setback along the Lester Street boundary is based on the greatest of 21 feet or the height of the building wall from the nearest edge of the travel lane. ****************************************************************************************** 2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s). 32. COMMENT: Label the building height and square footage of the building within the building footprint. The square footage of the outside dining area must also be labeled. Square footage of the building and the outside dining area must be listed in the zoning data text block. ****************************************************************************************** 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required. 33. COMMENT: If applicable draw and label the locations of any proposed monument signs. Add a general note stating that the signs will be permitted under separate permit. ****************************************************************************************** 2-06.4.9.X - Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-11.0.0, Landscape Plan Requirements. 34. COMMENT: See the landscape reviewer comments related to landscape buffers and screening. ****************************************************************************************** If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package site plan and any requested documents. |
06/22/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
06/29/2015 | JOE LINVILLE | LANDSCAPE | REVIEW | Reqs Change | 1) Landscape borders proposed in right-of-way or MS&R areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements. UDC 7.6.4.C.2.c 2) The site is required to include screening per UDC Table 7.6.4-I. Revise as necessary. UDC 7.6.5 3) Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting. UDC 7.6.4.C.2.e 3) Vegetation or structures higher than thirty (30) inches must be located outside of the sight visibility triangle Show required sight visibility triangles on the landscape plan. Plant materials located within SVT's should consist of ground cover or low-growing vegetation of a species that will not grow higher than (30) inches. However, trees may be planted within SVT's provided that: A) The trunk caliper, at maturity, will not exceed twelve (12) inches in diameter; B) The lowest branch of any tree is at least six (6) feet above the grade of the street, and C) Trees are not planted in a line that could result in a solid wall effect when viewed from an angle. UDC 7.6.5.E |
06/29/2015 | PGEHLEN1 | ADA | REVIEW | Passed | |
06/29/2015 | DAVID RIVERA | H/C SITE | REVIEW | Reqs Change | FROM: David Rivera Principal Planner PROJECT: DP15-0087 - Development Package 1801 N Stone Avenue Brother John's Barbeque Restaurant TRANSMITTAL DATE: June 29, 2015 DUE DATE: June 30, 2015 COMMENTS: 01. Label the running slopes for all sidewalk areas and accessible parking areas. 02. Label the slopes of the existing ramp at the south end of the building. Clarify if this ramp is part of an accessible ingress, egress or both. 03. Draw and label the accessible path from the accessible parking spaces to the main or multiple accessible entrance(s) of the building. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. |
06/30/2015 | JOE LINVILLE | NPPO | REVIEW | Reqs Change | Submit an NPP Plan. |
07/01/2015 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Reqs Change | TO: Michael Franks R.A. and Cypress Engineering DATE: June 30, 2015 SUBJECT: Engineering Review Development Package 1st submittal Engineering Review LOCATION: 1801 N Stone Av T14S R13E Sec1, Ward 3 PROJECT: Brother John's BBQ (previously the Wildcat House) FLOODPLAIN: FEMA zone X-unshaded, 2276L WATERSHED: Bronx Wash Watershed (TSMS DC) non-designated Basin Management Plan area REVIEWER: Elizabeth Leibold, P.E. PROJECT: DP15-0087 SUMMARY: Engineering has reviewed Development Package and does not recommend approval of the Development Package at this time until the following comments are addressed. MASTER COVER SHEETS/ GENERAL NOTES: 1) Admin Man Sec.2-06.4.7.6.a, B.2.b, Tech Man Sec.2-01: Address the following note comments: a) See Admin Man Sec.2-06.4.7 to assure missing general notes are added: A.2, A.6.a, B.1, B.3, & D. b) Add Scope of Work note on sheet AO.O, clarifying scope - state that parking area is to be restriped not re-paved nor regraded, state whether there is minor grading near building (whether there are changes in grades) and total disturbance in sqft. c) Call for Pre-construction meeting. For a PDSD Engineering Inspections, call IVR (791-3111), or schedule with a Customer Service Representative at the Planning & Development Services Department, or contact PDSD Engineering at 837-4888. d) There shall be no disturbance outside of these approved disturbance limits. Any disturbance outside of the disturbance limits requires separate permit or a submittal, review, and approval for separate permits. e) Permitee shall notify PDSD when construction operation is ready for final inspection. Final approval shall not be given until all work, including installation of all permanent erosion control measures, have been completed in accordance with approved plan and permit, and all conditions of permit are completed. BASE LAYER SHEET COMMENTS: 2) Admin Man Sec.2-06.3: Add DP15-0087 case number to Development Package sheets. 3) Admin Man Sec.2-06.4.8.G: Label accurate dimensions of property boundaries of project site. SITE PLAN SHEET COMMENTS: 4) Admin Man Sec.2-06.4.4.B&C: Clarify project-location map on sheet AO.O. a) Project-location map shall be located on first sheet in the upper right corner. b) Add scale (three inch equals one mile). c) Identify major streets within the square mile area and all streets that abut the subject property; d) Label section, township, and range, and section corners. 5) Admin Man Sec.2-06.4.8: Assure all existing utilities are shown and clearly labeled. Also, show and label existing fire hydrants on sheet AO1. 6) Tucson Code 25-39: Address the following radii comments: a) Stone Av is a MS&R Arterial Route; label on Site Plan planview sheet AO1. b) Label/show min. curb return radii of 25-ft for entrances off of Stone Av and 18-ft off of Lester St. 7) Admin Man Sec.2-06.4.8.C, 2-06.4.9.I: Label the following information regarding existing public right-of-way adjacent to the site: right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. LANDSCAPE COMMENTS: 8) Tech Man Sec.10-01.5.1.A.1: Show SVT's on sheets AO1, LO1, and AO3. Assure/adjust any proposed tree location is not in conflict with SVT's, or as applicable, add note with verbiage that clarifies that proposed trees within SVT areas shall be installed as mature enough to be pruned to meet SVT requirements so that lines of sight are not obscured between 30 inches and six feet. GRADING, PAVING, DETAIL SHEET COMMENTS: 9) Admin Man Sec.2-06.4.9.M.1, Tech Man Secs.2-01.4.1.C, 8-01.5.2.G: There is a concern for functioning positive gradient for drainage adjacent to building and in vicinity of ROW to show drainage flows within scuppers, not over sidewalk. Address the following grading comments: a) Clarify with cross sections and planviews how positive gradients and scuppers/outlets are provided at east side of building area through sidewalk - show existing and proposed grades. b) Add cross section(s) for south and east sides of building that includes existing and proposed elevations from building to road pavement, to include new concrete areas. c) Label and depict on grading sheet planview a local Basis of Elevation. 10) Tech Man Sec.8-01.5.2.D: Address the associated details regarding solid waste pick-up information: a) On detail 5 on sheet AO5, label dimensions between bollards and enclosure wall. b) Add note that gates shall be opaque (no see-through gates allowed). c) Label minimum 2% slope away within trash enclosure pad on planview sheet AO3. Include spot elevation information showing 2% positive gradient away from enclosure for solid waste pad area on sheet AO3. Assure solid waste pick-up area is elevated so as not to become a flowline for general local flows across the project site. DRAINAGE RELATED COMMENTS: 11) Tech Man Sec.4-04.2.3: Label scupper(s) at east side sidewalk that will accommodate flows from east side of building. 12) Tech Man Sec.4-04.2.3.1.4: show flow arrows for proposed conditions to clarify proposed drainage patterns on site and around proposed building. 13) Tech Man Sec.4-04.14.3.2(a)-(d) and 14.3.3: Consider providing either one of the following: a) Add these sections as general notes for maintenance for drainage facilities. Note may be edited to read only "drainage facilities" ("Owner or owners shall have an Arizona Registered Professional Civil Engineer prepare a certified inspection report for the drainage facilities at least once each year, and these regular inspection reports will be on file with the owner for review by City staff, upon written request". b) Or, add a note that a substantial completion statement will be provided, (for the project that specifically addresses constructed scuppers and positive gradient from building). UTILITIES / EASEMENTS COMMENTS: 14) Admin Man Sec.2-06.4.8.B, 2-06.4.9.L: All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. Assure complete information is provided for easements on the site. All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. Any easements should be recorded and the recordation information added to the development package prior to approval. Provide copy of title report in next submittal. STORMWATER POLLUTION PREVENTION PLAN COMMENTS: 15) If disturbance area exceeds 1 acre, a SWPP will be required. SOILS/GEOTECHNICAL REPORT COMMENTS: 16) No comment. Please provide a revised Development Package plan sheets, SWPPP, copy of title report, and comprehensive response letter that address the comments provided above. If you have questions, call me at 837-4934. Elizabeth Leibold, P.E., CPM, CFM Civil Engineer Engineering Division Planning & Development Services Department |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/14/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |