Permit Review Detail
Review Status: Completed
Review Details: REVISION - TENT PLAT & CORE RESUB
Permit Number - DP14-0248
Review Name: REVISION - TENT PLAT & CORE RESUB
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2016 | KROBLES1 | START | PLANS SUBMITTED | Completed | |
| 11/15/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The FFE of building 12 is 12" above the rim elevation of the next upstream manhole (MH #5, Rim 3009.50'; FFE, 3010.50') therefore no backwater valve may be installed for the building. The FFE of building 11 is less than 12" above the next upstream manhole and will require the installation of a backwater valve. ([Initial comment: Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, provide a note stating that a backwater valve shall be installed in the building drain or branch of the building drain serving that floor (e.g. see buildings 11, 13, and 14). Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.] |
| 11/15/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/16/2016 | LBOJORQ1 | ZONING-DECISION LETTER | REVIEW | Reqs Change |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2016 | LBOJORQ1 | APPROVAL SHELF | Completed |
| 11/16/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |
| 11/16/2016 | LBOJORQ1 | REJECT SHELF | Completed |