Permit Number: DP14-0145
Parcel: 115045090

Review Status: Completed

Review Details: DEV PKG - REVISION

Permit Number - DP14-0145
Review Name: DEV PKG - REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2015 CPIERCE1 START PLANS SUBMITTED Completed
04/07/2015 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Reqs Change please change or remove note 3 on cover sheet. This is not a Group Home
04/07/2015 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Reqs Change The revised Development Package has been reviewed on behalf of Environmental Services and following will need to be addressed on the resubmittal:
1. On Sheet C1.0, revise keynote 27 to state the concrete shall be 6 inches thick with #4 rebar spaced 12” O.C. both ways which is the required concrete construction per the figures in TSM Section 8.
2. On Sheet C1.0, revise the note regarding the staging area to read the maximum slope is 1.0% in any direction.
If there are any questions, I can be reached at kperry@perryengineering.net
04/08/2015 FDILLON1 DESIGN EXAMINER REVIEW Approved Development Package Revision 1 matches approved DRC approved Design Package - FD
04/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/10/2015 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required.
Please resubmit the following items:

1) Two rolled sets of the plans
2) A disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve this plan
04/10/2015 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved please change or remove note 3 on cover sheet. This is not a Group Home
04/10/2015 KBROUIL1 COT NON-DSD FIRE Reqs Change please change or remove note 3 on cover sheet. This is not a Group Home

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2015 AROMERO4 OUT TO CUSTOMER Completed