Permit Number: DP14-0143
Parcel: 13321074B

Review Status: Completed

Review Details: DEV PKG - REVISION

Permit Number - DP14-0143
Review Name: DEV PKG - REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2015 KROBLES1 START PLANS SUBMITTED Completed
11/10/2015 SSHIELD1 HC SITE REVIEW Approved
11/10/2015 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Wilmot Plaza
Development Package (Revision 3)
DP14-0143

TRANSMITTAL DATE: November 10, 2015

DUE DATE: November 19, 2015

1) Building #1 proposed square footage listed in letter, 6,737, Sheet 1 short & long term bicycle parking for Building #1 proposed square footage 6,382, Sheet 2 within the footprint of Building #1 6,737 + 645 patio = 7,382, clarify the differences. Clearly show the proposed patio area for Building #1.

2) Until the square footage has been clarified the required number of vehicle parking spaces cannot be verified.

3) Until the patio area is shown for Building #1 improvements for the sidewalks cannot be verified.

4) Reviewed

5) Reviewed but no revision cloud shown.

6) Reviewed.

Clarify why Cypress sheets 1 - 4 show revision 3 but on sheet 1 short term bicycle parking shows revision 4.

Once the above comments are addressed Zoning is willing to provide an over-the-counter review. Call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
.
11/17/2015 LOREN MAKUS ENGINEERING REVIEW Reqs Change Once the comments by the zoning reviewer are answered, I will approve this over the counter.
11/18/2015 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Two rolled sets of the plans
2) All items requested by review staff
3) All items needed to approve this plan
11/18/2015 JOE LINVILLE LANDSCAPE REVIEW Approved Pending zoning approval.
11/18/2015 JOE LINVILLE NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2015 EGALLET1 APPROVAL SHELF Completed
11/23/2015 EGALLET1 OUT TO CUSTOMER Completed
11/23/2015 EGALLET1 REJECT SHELF Completed