Permit Number: DP14-0143
Parcel: 13321074B

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP14-0143
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2014 AROMERO4 START PLANS SUBMITTED Completed
11/06/2014 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Wilmot Plaza
Development Package (3rd Review)
DP14-0143

TRANSMITTAL DATE: November 6, 2014

DUE DATE: November 20, 2014

The Zoning Review Section conditionally approves the development package for this project subject to the following conditions. However, should there be any changes requested by other CDRC members, the Zoning Review Section conditional approval is void, and we request copies of the revised development package to verify that those changes do not affect any zoning requirements.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

1. COMMENT: A hold has been put on the certificate of occupancy for building permit T14CM07545 until the recordation information for the following easements has been provided on the development package. The "10' ELECTRICAL EASEMENT TO BE ABANDONED" that runs under Building 6 and the "EXISTING COMMUMICATIONS EASEMENT" that runs under Building 1, will need to be abandoned prior to approval of the development package. Provide the recordation information on the plan.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
.
11/10/2014 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
11/10/2014 JASON GREEN ENGINEERING REVIEW Approved
11/14/2014 RONALD BROWN ZONING HC REVIEW Reqs Change SHEET 3
1. Note 15 references DTL 200 (concrete sidewalk) to a ramp that is located at the SE corner of the front building and provides access to the Broadway Blvd. right of way.
a. Provide a new note referencing the ramp to detail 8/9.
2. Note 36 references a railing to detail M/8 when it should be M/9.
3. Provide a new note referencing the ramp between the new and existing buildings to detail 7/9.
4. Reference comment 3 for ramp between two existing buildings to detail 3/4. Provide ramp width dimensions.
5. Insure all ramps have large scale details and are referenced to the proper details.
6. Insure that proper dimensions are provided at all large scale details.
SHEET 4
7. Provide a large scale detail for the steps handrail shown in detail 3/4.
END OF REVIEW
11/19/2014 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Two rolled sets of the plans
2) A disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve this plan
11/19/2014 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Reqs Change The Development Plan has been reviewed on behalf of Environmental Services and the following will need to be addressed on the resubmittal:

1. It is acknowledged that the NW egress point is now one way, exit only, however it is not clear the service vehicle can maneuver this exit and turn north while staying within the adjacent travel lane on Wilmot. As previously requested, show the turning maneuvers per the turning templates in TSM Section 8 on the plans.

2. The detail for the enclosure calls out the rebar reinforcement for the enclosure slab but not for the apron. Add the call out for the apron concrete reinforcement.

If there are any questions, I can be contacted at kperry@perryengineering.net

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2014 CPIERCE1 REJECT SHELF Completed