Permit Number: DP14-0026
Parcel: 11706168A

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0026
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2014 STEVE SHIELDS ZONING REVIEW Needs Review
02/19/2014 LHANLY1 ADA REVIEW Completed
02/19/2014 LOREN MAKUS ENGINEERING REVIEW Approved
02/19/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Completed
02/19/2014 LEERAY HANLY H/C SITE REVIEW Completed
02/20/2014 MARTIN BROWN FIRE REVIEW Denied Please provide detail(s) indicate how sliding gates(note 8) meets exiting requirements of 2012 IBC and IFC. Section 1008.1.4.4 indicate sliding gates not acceptable for A occupancies.
02/20/2014 FRODRIG2 NPPO REVIEW Needs Review
02/20/2014 FRODRIG2 LANDSCAPE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed