Permit Number: DP13-0153
Parcel: 141186130

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0153
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2013 MICHAEL ST. PAUL ZONING REVIEW Needs Review The grading plan appears to match the approve plat (S11-044). NPPO and Engineering approvals are required.
10/24/2013 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/28/2013,

SUBJECT: Discount Tires - Houghton Town Center
DP13-0153, T15S, R15E, SECTION 35

RECEIVED: Development Package on August 12, 2013

The subject submittal has been reviewed and it can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location on the Development Package where the revisions were made:

Drainage Report:

1. If the site drainage is designed to drain to the master detention basin, note this on the drainage exhibit and demonstrate this with grades and drainage arrows if possible.

Development Package:

1. Show sight visibility triangles at the Discount Tire driveway intersection with the East Access Drive (A.M. 2-06.4.9.H.2.).
2. If the site drainage is designed to drain to the master detention basin, note this on the plan exhibit and demonstrate this with grades and drainage arrows if possible (A.M. 2-06.4.9.N.1).
3. Show, if applicable, all proposed easements with recordation information as required by A.M. 2-06.4.9.L).
4. It is still not clear where the concrete channel, shown on Sheet DT2, is located. Clarify the location on the plan (A.M. 2-06.4.9.N.3).
5. Provide a detail of the proposed dumpster enclosure or call out the standard enclosure detail number (A.M. 2-06.4.9.T).

SWPPP:

The SWPPP report is acceptable.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov


RESUBMITTAL REQUIRED: Revised Development Plan Package and drainage report
10/29/2013 ANDREW CONNOR NPPO REVIEW Reqs Change Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2013 CPIERCE1 OUT TO CUSTOMER Completed
10/31/2013 CPIERCE1 REJECT SHELF Completed