12/10/2013 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Water Street - Multi Family Development
Development Package (Revision 5)
DP13-0080


TRANSMITTAL DATE: December 10, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. As a Board of Adjustment (BofA) or a Design Development Option (DDO) is required for elimination/reduction of the south landscape buffer Zoning cannot approve the plan until the BofA or DDO is approved. Once approved provide the BofA or DDo case number, date of approval, what was varied or approved, and any conditions of approval, on the site plan.

2. Once the comment above has been addressed Zoning is willing to provide an over-the-counter review. Call or email to schedule this review.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0080

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/10/2013 JASON GREEN ENGINEERING REVIEW Approved
12/12/2013 RONALD BROWN H/C SITE REVIEW Approved
12/12/2013 KEN BROUILLETTE FIRE REVIEW Approved
12/13/2013 ANDREW CONNOR NPPO REVIEW Approved
12/13/2013 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The landscape plan will contain the following identification in the lower right corner of each sheet:

Development Review Board (DRB) case; and/or,
Any other relevant case number for reviews or modifications that affect the site.

Including DDO date of approval and any conditions imposed.

ARTICLE 7: DEVELOPMENT STANDARDS

LANDSCAPING AND SCREENING

Street Landscape Borders

To enhance the visual appearance of the streetscape, a street landscape border is required in accordance with Table 7.6.4-1 along the street frontage of a site.

Minimum Width: Street landscape borders must be a minimum of ten feet wide as measured from the street property line.

Fifty percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. The required ground coverage must be achieved within two years from the date of planting.

Additional comments may apply
12/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan or an approved grading permit is not to be used for construction of on-site utilities (e.g. water service to buildings, building sewers, site lighting, or electrical service to buildings). The site utility plan shall indicate the locations of future site utilities but all construction notes for the on-site utilities shall be removed from the drawing. The construction of the on-site utilities serving multiple buildings shall be done with a separate permit.
2. Based on the sewer flow calculation on sheet C-3, units 1 - 5 will have a combined sewer flow of 3,000 gallons per day and will require review by PDEQ for a private sewer collection system (there is insufficient data on the plans to verify the daily sewer flow). A separate permit is required for the installation of a private sewer collection system that has been reviewed by PDEQ. Reference: Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code.
3. The water supply analysis on sheet C-3 is incorrect. The 2012 IPC does not have a Section 610.2 or a Section 610.12 and Appendix A is the "Plumbing Permit Fee Schedule". you appear to be using the 2012 edition of the UPC. Based upon the 2012 UPC (which can be used with an appeal to the building official), the water meters are undersized, the ¾" water service piping is undersized for a flow of 18 GPM, and the calculated water velocities are incorrect. Note that unless the pipe is galvanized carbon steel, a velocity exceeding 8 feet per second is not allowed. This will be addressed when the drawings are submitted for constructing the buildings and the on-site utilities.
4. Revise the drawing to provide the location and size of the public sanitary sewer, including the pipe diameter and the invert and rim elevations of all manholes; along with the Pima County Regional Wastewater Reclamation Department (RWRD) reference number.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/19/2013 CPIERCE1 REJECT SHELF Completed