| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2013 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approved | |
| 04/18/2013 | RBROWN1 | ADA | REVIEW | Passed | |
| 04/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/19/2013 | RONALD BROWN | H/C SITE | REVIEW | Denied | SHEETS C3.0 AND C4.0 1. Provide an accessible passenger loading zone as required by the 2012 IBC, Section 1106.7 and the 2009 Edition, ICC A117.1, Section 503. 2. Indicate that all slopes of all accessible routes comply with the 2009 Edition, ICC A117.1, Section 403.3; 5% maximum running slope and 2% maximum cross slope. SHEET C5.0 3. At detail 6: a. Delete all ADA references b. Detectable warning strips are not as per P.C./COT STD DTL 207. This is for COT/DOT right of way accessibility requirements only, not for private property. Private property detectable warning strip requirements are as per the 2009 ICC A117.1, Section 406.12, 13 and 14 as applicable. 4. At detail 5, reference comment 3, same notes apply. 5. At detail 4, provide a 7'-0" a.f.g. dimension line from the bottom of the larger sign. END OF REVIEW |
| 04/23/2013 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | The Arizona State Fire Marshal is the AHJ for the enforcement of the International Fire Code for Charter Schools. Plans should be submitted to the Phoenix office for review. KB |