Permit Number: DP12-0239
Parcel: 11303039A

Address:
3808 N 1ST AV

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0239
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2013 RBROWN1 ADA REVIEW Passed Not a COT owned and/or operated property
01/09/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: SSA Tucson - 3808 N. 1st Avenue
Development Package (1st Review)
DP12-0239

TRANSMITTAL DATE: January 10, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

The following comments are based on Development Standard 2-01.0:

1. D.S. 2-01.3.3 Provide the development package number, DP12-0239 adjacent to the title block on all sheets.

2. D.S. 2-01.3.7.A.6.b Provide a general notes stating "THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA SEC. 2.8.3, MAJOR STREETS AND ROUTES (MS&R) SETBACK ZONE".

3. D.S. 2-01.3.9.F All existing zoning classifications on and adjacent to the project including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. That said provide the zoning classification for the parcels located west of 1st Avenue.

4. D.S. 2-01.3.9.H.5.d The Long-term bicycle parking calculation is not correct. Based on a building gross floor area of 19,750 sq. ft./6000 the required number is 3.

5. D.S. 2-01.3.9.H.5.d It does not appear that the proposed Short-term bicycle parking location meets the requirements of LUC Section 3.3.9.3.B.1 & .3.

6. D.S. 2-01.3.9.J If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of -way lines, sight visibility triangles, etc.). That said show the future curb and sidewalk on sheet 2.

7. D.S. 2-01.3.9.L There is a concrete pad for a bus shelter called out under keynote 23. It appears that this bus shelter will be partially on private property, a access easement is required for the bus shelter.

8. D.S. 2-01.3.9.O The street perimeter yard setbacks, north and west, shown on sheet 1 under general note 19, and shown on sheet 2, are not correct. As 1st Avenue is shown on the COT Major Street and Routes map the required street perimeter yard setback is based on LUC Section 3.2.6.5.B for both 1st Avenue and Smoot Drive. The street perimeter yard setback for 1st Avenue is based on an average daily traffic (ADT) of 1,000 or greater and building height of 22', required perimeter yard setback to 1st Avenue is 22' measured from the back of future curb. Provide a perimeter yard setback dimension from the back of future curb, see comment 6, to the proposed building. The street perimeter yard setback for Smoot Drive is based on an average daily traffic (ADT) of over 140 but less than 1,000 and building height of 22', required perimeter yard setback to Smoot Drive is 22' measured from the outside edge of the nearest adjacent travel lane. Provide a perimeter yard setback dimension from the nearest adjacent travel lane to the proposed building.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov.

Sshield1 on DS1/planning/New Development Package/ DP12-0239

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
01/10/2013 LOREN MAKUS ENGINEERING REVIEW Denied Revise the sewer line through the basin. The inverts of the sewer line are at or above the bottom of the basin.
Clarify the property lines, current and proposed. Where property is to be dedicated, show the new property lines. Clarify the timing of the dedication. If the dedication along Smoot Drive will be completed before completion of the project, provide a 5-foot sidewalk along the whole street frontage.
Provide easements for areas where public access is being provided such as the proposed bus shelter location.
01/22/2013 RONALD BROWN H/C SITE REVIEW Denied SHEETS 2 AND 3
1. At the group of accessible parking spaces, please relocate the accessible parking signage so as not to be hidden by aged landscaping.
2. Insure that all accessible route slopes comply with ICC A117.1, Section 403.3; 5% max running and 2% max cross.
END OF REVIEW
01/23/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water and as close as practicable to the service connection. Verify the proposed location is acceptable to Tucson Water. Reference: Chapter 27, Article V, Section 27-76 (a), Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
2. The rim elevation of the next upstream sanitary manhole (2344.57') is less than 12" below the first floor elevation (2345.00'). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
3. The building sewer is shown traversing the retention basin but with the invert of the building sewer at2340.72', the top of the pipe will be about 6.6" above the bottom of the basin (2340.50'). A minimum cover of 12" is required over the building sewer.
4. The site plan shows an un-metered 2" water service to the south side of the building. Please clarify.
01/24/2013 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Note the height of existing screen walls proposed to meet the requirements of LUC Table 3.7.2-I.
01/24/2013 JOE LINVILLE NPPO REVIEW Approved
01/25/2013 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2013 CPIERCE1 REJECT SHELF Completed