Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP12-0217
Parcel: 10510253A

Address:
4280 N 1ST AV

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP12-0217
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 DAVID RIVERA ZONING REVIEW Approved
01/24/2013 JASON GREEN ENGINEERING REVIEW Approved January 24, 2013
FLOODPLAIN USE PERMIT NO.: T13OT00070
ADDRESS: 4280 N 1st Street Tucson, Arizona 85719
PROPERTY OWNER: Vantage West Credit Union
2480 N Arcadia Ave Tucson, Arizona 85719

The applicant is authorized to use a portion of the City of Tucson Flood Hazard Area per the Rillito Crossing Market Place, Site Drainage Report (Project Number 3050121) created by National Survey and Engineering, signed and sealed by Justin Turner (CN 15293) November 14, 2005, specifically described as:

A portion of Parcel 105-10-253A, Rillito Crossing Market Place PTN Lot 1 & PTN Lot 1 & Lot 2 Exc PTN S9.49'

For the purpose of constructing a new commercial building and associated infrastructure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 9 conditions:

1) This project is located in a mapped regulatory floodplain per the Site Drainage Report (Project Number 3050121) created by National Survey and Engineering, signed and sealed by Justin Turner (CN 15293) November 14, 2005.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) All work shall conform to the approved development plan package prepared by Oracle Engineering Group, Inc. which is made part of this permit.

4) For purposes of this permit the following flood elevations shall be used for the Finished Floor Elevation of the new building:
Base Flood Elevation (BFE) = 2324.0 feet NAVD 1988
Regulatory Flood Elevation (RFE) = 2325.0 feet NAVD 1988
Building is to have lowest finished floor elevated at or above the Regulatory Flood Elevation (RFE) and lowest point of any attached appliances is to be at or above the Regulatory Flood Elevation (RFE).
5) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the 1010/1015 inspection (P2S) and prior to finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the building as well as the identity and location of all other equipment/machinery servicing the building.

6) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T13OT00070 FOR INFORMATION PLEASE CALL 791-5550."

7) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

8) All work shall conform to the approved site plan, DP12-0217, which is made part of this permit.

9) This permit is specific to the improvements for 4280 N 1st Ave as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Metro TED
ADDRESS: 88 W Cushing St Tucson, Arizona 85701
PHONE: 520-990-6866
OWNER: Vantage West Credit Union
ADDRESS: 2480 N Arcadia Ave Tucson, Arizona 85719
PHONE: 520-298-7882

(EXPIRATION DATE) Month: 01 Day: 24 Year: 2014

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
01/28/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved
02/04/2013 RONALD BROWN HC SITE REVIEW Denied 1. At sheet C2.0, the most northerly sidewalk ramp at the most southerly marked crossing is not relative to note 8 reference detail 4/C4.0. Provide a separate detail complying with section 405 of the 2003 ICC A117.1.
2. Detail 4/C4.0 is a DOT detail referencing to a drive curve. Please provide a compliant curb ramp detail as per the 2003 ICC A117.1, Section 406, Curb Ramps. Insure 1:10 flared sides if so incorporated.
3. Add a new note 37 on sheet C2.0: "All new accessible routes and marked crossings to have a max running slope of 5% and a max cross of 2%".
END OF REVIEW