Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP12-0217
Parcel: 10510253A

Address:
4280 N 1ST AV

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0217
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2012 JASON GREEN ENGINEERING REVIEW Denied DATE: December 17, 2012
SUBJECT: Vantage West Credit Union Development Plan Package- Engineering Review
TO: Metro TED Attn: Lisa Bowers
LOCATION: 4280 N 1st Ave; T13S R13E Sec24
REVIEWERS: Jason Green, CFM
ACTIVITY: DP12-0217

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package and Drainage Statement (Oracle Engineering Group, Inc., 15NOV12). Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under Development Standard 2-01. The following items need to be addressed:

SITE PLAN:

1) DS Sec.2-01.3.2.E: Revise the title block on the development plan document to include the page number and number of pages of all sheets that are included within the set (i.e. Landscape Sheets).

2) DS Sec.2-01.3.3: The relevant Development Plan Package number (DP12-0217) may be added to the lower right hand corner of the plan on all sheets.

3) DS Sec.2-01.3.7.A.6.b: Provide a General Note on the Development Plan Package that references all special overlay zones that are applicable to this site, specifically state that "the project is designed to meet the overlay zone criteria for Sec.2.8.3 Major Streets and Routes (MS&R) Setback Zone." It is acknowledged that General Grading Note #23 states conformance, but it does not read per the referenced Development Standard.

4) DS Sec.2-01.3.7.B.2: Provide a Floodplain Use Permit Application for this project per General Note #8 and the Rillito Crossing Market Place, Site Drainage Report (Project Number 3050121, created by National Survey and Engineering, signed and sealed by Justin Turner (CN 15293), November 14, 2005 that established a minimum finish floor elevations for the required Elevation Certificates.

5) DS Sec.2-01.3.8.B: Revise the development plan document to label the recordation information for all existing easements, provide recordation information, location, width, and purpose of on the development plan document. Specifically the private sign easement and the cross access easement per the final plat, S05-207.

6) DS Sec.2-01.3.9.H.5: Revise the development plan document and Detail 5 on Sheet c4.0 to correctly dimension the required 2.5-foot overhang from the front of the curb stop to the curb and sidewalk.

7) DS Sec.2-01.3.9.R: Refer to comments from Ron Brown, RA Structural Plans Examiner for all handicap accessibility comments that may be associated with this project.

8) DS Sec.2-01.3.9.T: Revise Detail 10 on Sheet c4.0 of the development plan document to reference the correct concrete thickness per DS Sec.6-01 and Figure 3b. Detail 9 correctly references the 6-inch thickness, revise Detail 10 to match.

GENERAL COMMENTS:

Please provide a revised Development Plan Package that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon re-submittal of the Development Plan Package. For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
11/20/2012 RBROWN1 ADA REVIEW Passed
12/06/2012 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0217
4280 N. 1st Av.
Development Package

TRANSMITTAL: 12/10/2012

DUE DATE: 12/18/2012

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 11/18/2013.

2. DS 2-01.3.2. The title block shall include the following information.
B. A brief legal description
E. Page number and number of pages. Landscape plans are to be included in the page numbering.

3. DS 2-01.3.3 This project has been assigned case number DP12-0217. Place this number near the lower right corner of all sheets

4. DS 2-01.3.7.A.4 Identify the existing and proposed use of the property as classified per the Land Use Code. List all Land Use Code sections each proposed use is subject to.
General note #4 should read as follows: "Financial Service "31", subject to: Sec. 3.5.13.5 and Sec. 3.5.4.5.C". Note on the plans the wrong development designator (8) has been used, the correct development designator is "31". Revise notes and calculations..

5. DS 2-01.3.7.A.6.b Provide as a general note the following: This site has been designed to meet the criteria of Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone.

6. DS 2-01.3.7.A.9.b In the project information section of sheet 2 of 8 the allowed FAR per LUC Sec. 3.2.3.2.B with a development designator 31 is 0.90. Revise note.

7. DS 2-01.3.9.H.5.a Detail 5 on sheet 4 of 5 indicates a wheel stop at 3' from the front of the parking space. Per LUC Sec. 3.3.6.8.C When required, wheel stop curbing must be two and one-half (2½) feet from the front of the parking space. Revise detail.

The total number of provided parking spaces in the project information portion of sheet 2 of 8 is not correct. Per a count of the vehicle spaces on the plan a total of 34 spaces are being provided. Revise note.

Clearly indicate the location of the required 3 stacking spaces at the drive thru area for each lane. See LUC Sec. 3.3.7.1

Per LUC Sec. 3.3.7.2.D Drive-through lanes must be striped, marked, or otherwise clearly delineated. Comply.

8. DS 2-01.3.9.H.5.d A loading zone is not required for this project. If a loading zone is to be provided revise the note in the project information portion of sheet 2 of 8. Should read as follows: loading zone: none required and 1 - 10X18 provided. Revise.

9. DS 2-01.3.9.H.5.d Provide a dimensioned detail of the required short term and long term bicycle parking spaces, clearly indicating the size of the parking spaces, the required 5' access aisle, type and size of the long term bicycle locker, etc.. Review LUC Sec. 3.3.9.3 and 3.3.9.4 for criteria.

Revise notes to indicate short term and long term bicycle parking spaces. No longer are the classified as class one and class two.

10. DS 2-01.3.9.O Provide a dimension from the building to the back of future curb.

In the project information on sheet 2 of 8 the indicated required setback along 1st Av. is 21' or the height of the wall of the structure (which ever is greater) from the back of future curb. Revise note.

11. DS 2-01.3.9.Q On the foot print of the building on sheet 2 of 8, provide the overall dimensions of the building footprint.

Provide in the project information portion the maximum allowed height of the building (30' per rezoning condition #19) and the provided height of the structure.

12. DS 2-01.3.9.W Per the final plat (S05-207) there is a private sign easement indicated. Provide on the plan the location, use, and recording information for this easement.

Per the final plat (S05-207) there is a cross access easement indicated which affects this property. Clearly indicate location, use, and recording information for this easement on the plan.

13. DS 2-01.3.7.A.2 The total square footage and acreage of this site as indicated in general note #3 and the project information on sheet 2 of 8 is not correct. Per the final plat, S05-207, the total square footage is 55,634 and 1.27 acres. Revise FAR calculations, general note #3, general note #6 and project information notes.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\DP12-0217dp.doc
12/14/2012 RONALD BROWN H/C SITE REVIEW Denied SHEETS C2.0 AND C3.0
1. Note 8, for all ramps shown with the marked crossings, detail 4/C4.0 in not a compliant detail as required by ICC A117.1, Sections 405 and/or 406. Please revise ramp detail to meet these requirements and resubmit.
a. Detectable warning strip requirements are to be as per ICC A117.1, Sections 406.12, 13 and/or 14 as applicable for the design.
b. For sidewalk ramps provide a separate detail also showing detectable warning strips if part of a marked crossing. Detectable warning strips are not required for entry to an accessible parking aisle unless it also is part of a marked crossing.
2. Please note accessible route slope compliance with ICC A117.1, Section 403.3; 5% max running and 2% cross slopes.
3. Finish the east end of the marked crossing to the dumpster. Provide a curb ramp, landing and detectable warning strip.
SHEET C4.0
4. Detail 4 is not code compliant. Reference ICC A117.1, Section 406. Revise and resubmit.
5. At detail 2, the bottom of the main sign is to be 7'-0" as required by COT DOT standards.
6. Detail 5 is not the same parking layout as designed and shown on the site plan. Please revise to make the same and show all accessible requirements such as dimensions, signage, ramps, accessible routes, markings, aisles and grade slopes as per 502.5.
END OF REVIEW
12/18/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Provide previous approved site and landscape plans for reference.

2. Provide both the proper and common name of existing plant material DS 2-07.2.2.A.1.d.

3. Identify screening elements on the landscape plan DS 2-07.2.2.A.3.a

4. Note: Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B

5. Ensure that all Zoning & Engineering comments and concerns are addressed.

6. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

7. Additional comments may apply
12/18/2012 ANDREW CONNOR NPPO REVIEW Approved
12/18/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/19/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/21/2012 JOHN BEALL URBAN PLANNING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2013 CPIERCE1 REJECT SHELF Completed