Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP12-0198
Parcel: 205640620

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0198
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
11/06/2012 PAUL MACHADO ENGINEERING REVIEW Approv-Cond
11/07/2012 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2012 CINDY AGUILAR OUT TO CUSTOMER Completed