Permit Number: DP12-0033
Parcel: 14041127A

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - DP12-0033
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2013 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: October 16, 2013
TO: Justin Schmidt EIT, Project Engineer I, Jim Roth, P.E., COLE Engineering
SUBJECT: Tire Warehouse Final Revised Grading Plan re-submittal Engineering Review (Revision #2)
ADDRESS: 6720 S ALVERNON WY 85756, Ward 5
LOCATION: T15S R14E Section 16
FLOODPLAIN: FEMA zone X, 2293L
REVIEWER: Elizabeth Leibold, P.E.
ACTIVITY NUMBER: DP12-0033

SUMMARY: This submittal included the correctly sealed letters and as-builts for the Tire Warehouse grading permit completion documentation. Engineering has reviewed the resubmittal for the Final Revised Grading Plan and recommends Engineering approval. Please be aware that any outstanding Inspections need to be closed out prior to final approval for completion; this includes any required corrections for NPPO/landscaping per the NPPO Monitoring Report dated October 2, 2013, which was submitted in this last submittal package.

If you have questions, call me at (520)837-4934 or Andy Connor (NPPO inspection) at (520)837-4950.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division, Planning & Development Services Department
City of Tucson

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2013 CPIERCE1 OUT TO CUSTOMER Completed