Permit Number: D11-0019
Parcel: 11706168A

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D11-0019
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/25/2011 RONALD BROWN ADA REVIEW Passed
06/27/2011 DAVID MANN COT NON-DSD FIRE Approved
06/30/2011 TIM ROWE PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


June 29, 2011

To: THOMAS SAYLER-BROWN
SBBL, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: RIALTO BLOCK PATIO
Dev. Plan - 1st submittal
D11-0019

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
1. Obtain a letter from the PCRWRD's Development Liaison Unit, written within the past year, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/developer.htm#permits

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

2. Revise Wastewater Note # 2 to:

THE ON-SITE SEWERS ARE EXISTING AND PRIVATE. NO NEW SEWERS ARE PROPOSED.


3. Remove Miscellaneous Note # 3 since no new sewer has been proposed.

4. Show the existing public sewer line in Herbert Ave. and call out the width of the public alley.

5. Call out the rim and invert elevations for the existing public sewer manholes on plan.

6. Create a Legend showing symbols for all sewer elements existing/proposed/public and private.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second(2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder
07/12/2011 LEERAY HANLY ZONING HC REVIEW Approved
07/12/2011 PATRICIA KRAUSMAN DESIGN EXAMINER REVIEW Approved The DE recommends approval. Thanks. Adam Smith
07/15/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Approved Review conducted by Zelin Canchola

TDOT Traffic has no adverse comments
07/20/2011 LOREN MAKUS ENGINEERING REVIEW Denied July 20, 2011
D11-0019
Rialto Block Patio

The Engineering Division does not recommend approval of this development plan at this time. The following comments must be addressed.

1. Clarify the area encompassed by this development plan. The notes indicate the site has a gross area of 35,629 square feet. Clearly delineate this area. (DS 2-05.2.3.A)
2. Provide the legal description for the entire site. (DS 2-05.1.G.2)
3. We understand the Rialto Theatre is not a part of this DP. Indicate this by using different line weights and notes. (DS 2-05.2.3.H)
4. Clearly delineate the boundary lines for the existing parcels within the site with distances and bearings. The underlying subdivision lot lines should be eliminated or lightened. (DS 2-05.2.4.A)
5. Provide the correct page reference in the detail call-out.
6. Provide a location map as described in DS 2-05.1.D. Show the location approximately centered within a one square mile area, with a minimum scale of 3"=1 mile. Show conditions within the square mile area including major streets and watercourses. Label the section, township and range; section corners; north arrow and scale. (DS 2-05.2.3.A)
7. Show the size and location of the storm drain line and inlet. (DS 2-05.2.3.F)
07/21/2011 JOE LINVILLE LANDSCAPE REVIEW Approved
07/25/2011 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D11-0019
Rialto Block Patio
Development Plan

TRANSMITTAL: 07/25/2011

DUE DATE: 07/25/2011

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is .6/23/2012.

2. DS 2-01.2.5 The 3x5 inch space on sheet DP-1 is to be reserved for county approvals. Please move the CDRC approval stamp outside of the 3x5 space.

3. DS 2-01.2.7 The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet.

4. DS 2-01.3.2 In the title block the legal description should include the entire site (portions of lot 10 and 11 etc.)

5. Ds 2-01.3.4 The project-location map shall cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information.

A. Section, township, and range; section corners; north arrow; and the scale will be
labeled.

6. DS 2-01.3.7.A.4 Identify the existing uses of the property as classified per the LUC. Include all existing uses within the .82 acre.

7. DS 2-01.3.7.A.6.b List the overlay zones applicable to the property. Such as: Sec.2.8.4 Gateway Corridor Zone, Sec.2.8.10 Rio Neuvo and Downtown, Sec.2.8.7 Downtown Heritage Incentive Zone, Sec. 2.8.3 major Streets and Routes, etc.

8. DS 2-01.3.8.A Provide the distance and bearings of all lot lines. Remove the Rialto Theater parcel from the plans, does not appear to be part of this proposal.

Per the assessors tax parcel maps the indicated lot lines are not correct. Clearly indicate the location of all property lines.

Remove the underlying subdivision property lines

9. DS 2-01.3.8.B If applicable, All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated.

10. This plan has been assigned case number D11-0019. Place the case number near the lower right corner of all sheets.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D11-0019dp.doc
07/26/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

July 26, 2011

Thomas Sayler-Brown
SBBL Architecture
1001 N. Alvernon Way
Tucson, Arizona 85711

Subject: D11-0019 RIALTO BLOCK PATIO Development Plan

Dear Thomas:

Your submittal of June 24, 2011 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 4 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan (Wastewater, Engineering, Zoning, PDSD)

1 Check Made out to “Pima County Treasurer” for $50.00 (Wastewater)


Should you have any questions, please call me at 837-4893.


Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/