Permit Number: D10-0036
Parcel: 11943001A

Address:
1655 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0036
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2010 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/24/2010 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 2ND FL
TUCSON, AZ 85701-1207


AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D10-0036 SOLAR ARRAYAT PLAZA DEL SOL/REVISED DEVELOPMENT PLAN
DATE: November 24, 2010



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

On the Final Development Plan:
Add Drive to Freedom.
Change Quicktrip #1470 Book 63 to Book 65.
Delete Via Revenna Soud per letter dated 11-2-10.
Delete South from South Valley Road per letter dated 11-2-10.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.
11/24/2010 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 2ND FL
TUCSON, AZ 85701-1207


AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D10-0036 SOLAR ARRAY AT PLAZA DEL SOL/REVISED DEVELOPMENT PLAN
DATE: December 21, 2010



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
12/01/2010 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D10-0036 SOLAR ARRAY at PLAZA DEL SOL - Ajo Way

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations

CROSS REFERENCE: SE-10-122, Plaza Del Sol

NEIGHBORHOOD PLAN: Santa Cruz Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: December 08, 2010

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
(X) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(X) Resubmittal Required:
() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Other


REVIEWER:msp 791-5505 DATE: 11/30/10
Planning and Development Services Department
Community Planning Section
D10-0036 - Solar Array at Plaza Del Sol - Ajo Way
November 30, 2010

The site is zoned MH-1, a mobile home park zone and requires a Special Exception approval to allow the proposed solar renewable energy generation facility in the MH-1 zone. Based on the applicant's request, a concurrent review of both the Special Exception and development plan are being conducted by staff. Prior to the approval of development plan D10-0036, it shall comply with any and all conditions approved through the Special Exception process. Therefore, the following revisions to the development plan, as outlined by staff are subject to the Special Exception, as may be approved/modified by Mayor and Council at a future date. Any changes by Major and Council on the Special Exception consideration shall be addressed by the applicant prior to resubmittal of the development Plan.

Staff offers the following comments:
1. Prior to development plan approval, provide written notice from the City's Real Estate Office (Jim Rossi) that their office is reviewing this project for a one-foot no access easement along Valley Road, along that portion of the mobile home park's eastern perimeter that will be utilized by the solar renewable energy generation facility.

2. The proposed chain link fence with slats and native landscape border is supported within the mobile home complex, which is to screen the western perimeter of the solar renewable energy generation facility. However, a chain link fence is not supported along the southern or eastern perimeter, which abuts adjacent residentially developed parcels and the Santa Cruz River Linear Park Corridor. Please revise (all applicable sheets) on the development plan and the landscape plan, by deleting verbiage, key notes, and cross-section information that states an option to use "chain link fence with slats" along the southern and eastern perimeters of the solar renewable energy generation facility. Revise the southern and eastern perimeter landscape border/wall description/keynotes/cross-sections to match language, key notes, and cross-sections, as shown on the original development plan submittal dated October 27, 2010. The option to use chain link fence with slats on the southern and eastern perimeter was revised by the applicant on the 2nd submittal without discussion with staff. This proposal is not supported by Plan policy along exterior perimeters.

3. Please revise development plan (landscape section) sheet 17 of 23 to show the Drought-Tolerant Native Landscape border, adjacent to the full length of the proposed chain link fence with slats along the western perimeter. Current submittal shows native landscape at approximately one-fourth the total length of the western perimeter.

The drought-tolerant native landscape border along the western perimeter shall be shown from the southwest corner of the solar renewable energy generation facility, going north and northeast along the western perimeter to the point where the chain link fence connects to the proposed masonry wall that is shown along the northern, eastern and southern perimeters.
12/06/2010 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond TDOT usually requires a 1/4-inch minus material in ROW areas. Revise the final plans as necessary.
12/07/2010 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner Zoning Review Section

PROJECT: D10-0036
165 W. Ajo Way
Solar Array at Plaza Del Sol
Development Plan

TRANSMITTAL DATE: December 7, 2010

DUE DATE: December 08, 2010

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section approves the development plan package for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is November 11, 2011.

2. This development package is conditionally approved with the acknowledgement of the developer that the Special Exception review and approval process is concurrent and is subject to possible conditions that could result in revisions to the development plan package. All previous zoning comments have been addressed with regards to the development package review.

Additional comments may be forthcoming based on the special exception conditions of approval. Please be aware that the development plan may not be fully approved until the special exception process is completed and when all conditions of the special exception approval have been incorporated into the development plan. (a conditional approval from CDRC may be possible but permits may not be issued until all requirements have been addressed.)

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

DGR C:\planning\cdrc\developmentplan\D100036dppca.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan if additional conditions are added to the preliminary set of conditions.
12/09/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied DATE: December 9, 2010
TO: John R. Calvert / President and CEO, Cal Energy Group
SUBJECT: Plaza Del Sol Solar Array Development Package Engineering Resubmittal
ADDRESS: 1655 W Ajo Wy
LOCATION: T14S, R13E, Sections 34/35
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN STATUS: FIRM Panel: 040076 2236K (effective date 2/8/99), SFHA zone: AE.
ACTIVITY NUMBERS: T10BU01638, D10-0036, T10OT02322

SUMMARY: PDSD Engineering Division has reviewed the plan set resubmittal, and does not recommend approval of the Development Package, grading permit, or Floodplain Use Permit applications until the special exception process is completed.

COMMENT:
1) Special Exception process with any Conditions must be completed as discussed in correspondence and meetings prior to final approval of Development Package.

If you have any questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
12/13/2010 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
12/14/2010 FRODRIG2 ENV SVCS REVIEW Approved Date Case Number Project Address
December 7, 2010 D10-0036 Solar Array at Plaza Del Sole
DEVELOPMENT PLAN

Comments: The proposed Development Plan for the Solar Array at Plaza Del Sole,
Case No. D10-0036, meets the minimum requirements for Environmental Services
Solid Waste Disposal and Recycle materials Standard 6-01.0 and is here Approved.

Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
12/14/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES


December 14, 2010

Gary Grizzle
The WLB Group
4444 E. Broadway Blvd.
Tucson, Arizona 85711

Subject: D10-0036 SOLAR ARRAY AT PLAZA DEL SOL Development Package

Dear Gary:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made, please submit the following documents for sign-off.

1 Rolled blue line COMPLETE SET of the Development Package, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional black line copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your plans to the CDRC office for sign-off approval.

*** NOTICE *** PRIOR TO SUBMITTING TO CDRC, YOU WILL NEED TO TAKE THE PLANS TO PIMA COUNTY ADDRESSING FOR APPROVAL. WE WILL NEED THE APPROVAL IN WRITING (EMAIL IS OKAY) FROM ADDRESSING BEFORE CDRC CAN ACCEPT THE SUBMITTAL.

Plans will not be signed and released until the CDRC office has been notified by PC Addressing that all fees for this plan have been paid. The CDRC office will need this confirmation in writing

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4893.
Sincerely,


John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/