Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D07-0041
Parcel: 133033000

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0041
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/05/2008 FRODRIG2 PIMA COUNTY WASTEWATER Denied February 5, 2008


To: John Holley
The WLB Group

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Tanque Verde Valley Casitas
Dev. Plan – 2nd Submittal
D07-041


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

This project will be tributary to the Ina Road Wastewater Treatment Facility via the North Rillito Interceptor. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office. 2nd Request.

Sheet 4: Call out the size of pipe and construction plan# for the existing sewer line in Arbor Cr..

Sheet 1: Include symbols in the Legend for the existing sewer line and elements.

We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of residential lots. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of the Final Plat.

This office will require a revised set of blue lines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the third(3rd ) submittal. A check for the review fee of this submittal in the amount of $78.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of blue lines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
02/27/2008 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0041 TANQUE VERDE VALLEY CASITAS/REVISED DEVELOPMENT PLAN
DATE: February 26, 2008


The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.





jg
02/29/2008 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D07-0041
Tanque Verde Casistas
Development Plan

TRANSMITTAL: 02/29/2008

DUE DATE: 11/01/07

COMMENTS:

1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. The sidewalk located along the south property line adjacent to Speedway appears to be located in the required landscape buffer. Approval by Landscape required.

3. Provide the date of approval for the DSMR in note #28.

4. Provide docket and page recordation information for the right of way dedication.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D07-0041dp.doc
03/03/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
03/05/2008 JOE LINVILLE LANDSCAPE REVIEW Approved
03/06/2008 LOREN MAKUS ENGINEERING REVIEW Denied March 6, 2008

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Tanque Verde Valley Casitas
Development Plan D07-0041 (Second Review)
T14S, R15E, Section 2

RESUBMITTAL REQUIRED: Revised Development Plan

The development plan has been reviewed by the Engineering Division and we do not recommend approval at this time. The following comments must be addressed:

1. As previously commented, this proposed development appears to be in violation of the differential grading requirements of the grading Development Standard. Revise the proposed grades to limit the fill in the outer 100 feet of the project site to less than 2 feet (excepting the filling of minor depressions and holes.) If the additional fill is unavoidable, follow the procedure for approval outlined in the development standard.
2. Provide sufficient cross sections and details to show how the project will accept off-site drainage in the same manner and locations as shown in the existing conditions. This especially applies to the area near the west end of the south parking area. It is unclear in this area whether the drainage from drainage area 1.1 OS is allowed to enter the project area.
3. Clearly indicate in the details where the retained soil is for each wall. Indicate the approximate maximum retained depth for each section of retaining wall.

Drainage Report:

The drainage report is accepted for development plan purposes.


If you have any questions, I can be reached at 520.837.4927 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
03/06/2008 FRODRIG2 COT NON-DSD REAL ESTATE Denied I did not receive the legal description and sketch for the right of way dedication along Speedway. Please send this legal description and sketch directly to me at the following address or e-mail. Also, I will need a title report for the subject development dated within 30 days.

Sincerely,

Jim Stoyanoff
Property Agent
Real Estate Program
City of Tucson
201 N. Stone Ave. 6th Fl.
Tucson, Arizona 85701
(O) 520.837.6719
(F) 520.791.5641
Jim.Stoyanoff@tucsonaz.gov
03/10/2008 ANDY VERA ENV SVCS REVIEW Approved In ground container enclosure detail okay.

** Review done at DSD due to mailing issue.
03/13/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 13, 2008

John Holley
The WLB Group Inc.
4444 East Broadway Blvd.
Tucson, Arizona 85711

Subject: D07-0041 Tanque Verde Valley Casitas Development Plan

Dear John:

Your submittal of February 4, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

5 Copies Revised Development Plan (Wastewater, Zoning, Real Estate, Engineering, DSD)

3 Copies Revised Landscape Plan (Zoning, Engineering, DSD)

2 Copies Legal Description and Sketch (Landscape, DSD)

2 Copies Title Report (Real Estate, DSD)


Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 881-7492
dp-resubmittal