Permit Number: D04-0004
Parcel: 10602043D

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - DEVELOPMENT PLAN

Permit Number - D04-0004
Review Name: RESUBMITTAL - DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/29/2004 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Revised landscape plans are required for development plan approval. Development and landscape plans are to clarify compliance with the screening requirements of LUC Table 3.7.2-I. Note the height of any required screen walls.
06/29/2004 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D04-0004 FAMILY DOLLAR STORE / STONE
DATE: JUNE 29, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1. Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2. All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
07/07/2004 JCLARK3 ENV SVCS REVIEW Denied Response note on sheet C-1 does not say anything about casters or a roll out type of service.
Shown enclosure is across a sidewalk area. Do not know if this is allowed and if allowed the sidewalk has to be thicker than standard.
Enclosure is shown on a future pat site. The enclosure should be permanent for the building being constructed.
Enclosure should be detailed and not labeled per standard. There aes no set detail for enclosures. (The standards give typical dimensions such as 10 feet clear, bollard for side and rear wall protection, doors, and a typical section showing construction material and height.)
The City is servicing other Family Dollar stores in the Tuuson area. These stores have enclosures for recycling containers and usually each store has one or two containers just for recycling. The response does not seem appropriate.
07/08/2004 BLANCA ESPINO ENGINEERING REVIEW Denied The following items must be revised or added to the plan. Please include a response letter with the next submittal that states how all comments have been addressed.

1. All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes. D.S. 2-05.2.1.C Correct and revise all text overlays and text heights to be equivalent of 0.12" point or greater. Utility symbols indicating location on site require revision.

2. As per the added note, "Drainage will remain in its natural state and will be altered, disturbed, or obstructed other than as shown on this development plan." This note is to be enforced with all development. As per Sheet C-2 proposed grades have been altered to direct drainage into a different direction. Demonstrate justification as to proposed grades and also how it may have an impact on adjacent properties.

3. Indicate contour intervals along with north arrow and scale, which should be placed together on each sheet, preferably in the upper right corner of the plat. D.S. 2-05.2.1.H Correct and revise sheet C-1.

4. A legend that shows and describes all symbols used on the drawing is to be placed on the plan, preferably on the first sheet. Indicate symbol for existing and proposed grading points and any information symbolizing drainage issues. D.S. 2-05.2.1.J Correct and revise all existing and proposed elevations to indicate Top of Curb = TC and or Top of Pavement = TP. Grading Plan is being viewed for existing and proposed grading and drainage conditions in comparison to the development plan. Sheet C-3 indicates a symbol of an existing light pole in the legend but on the plan and Sheet C-2 indicates a different symbol. Sheet C-1 indicates same symbol as C-3 but labeled as existing street lamp. Apply corrections to all sheets.

5. Symbols to be indicated in Legend; existing and proposed TC & TP elevations, existing 60" wall, 30' screen wall, WSE, grade break, Q100 qty. of inflow/outflow with arrow, proposed inlet, downspouts, survey monument, existing fire hydrant, clear valve (?) symbol just southwest of street intersection, street lights, etc.

6. Identify symbols on site that are not noted in the legend. Indicate symbols in legend; Sheet C2 indicates two symbols on either side to the store entrance, three black dots in front of handicap parking area and refuse collection area. Identify utility symbol with dashed lines with a "T". Identify utility symbol with dashed lines with a "x".

7. Indicate information for survey monuments as per COT Records of survey such as; elevation, description, location, benchmark identification number.

8. Indicate information for sewer, water and storm drain manholes including pipe diameter, reference number, invert and rim elevations of all manholes and cleanouts.

9. Sheet C-3 indicates a symbol for an existing power line but not for an existing underground power. Indicate if these two items are the same or individual utilities. Indicate revised symbols for the existing underground power in the legend. Correct and revise.

10. Remove #22 from General Note of Cover Sheet.

11. As per D.S. 10-01.0.0 Stormwater Detention/Retention Manual and D.S. 10-02.0.0 City of Tucson SMDDFM, are required for all Development Plans. Refer to SMDDFM.14.3.1-4 for Inspection and Maintenance Polices. Indicate which paragraphs apply to the site conditions. D.S. 10-01.0.0 refers to SDRM 1.4 D.S. 10-02.0.0 refers to SMDDFM 1.5 thru 1.5.2

12. The development plan shall have a note stating (a) that the owner or owners shall be solely responsible for operation, maintenance, and liability for drainage structures and detention basins; (b) that the owner or owners shall have an Arizona Registered Professional Civil Engineer prepare a certified inspection report for the drainage and detention/retention facilities at least once each year. SMDDFM 14.3.2 Indicate statement in Drainage Report.

13. Indicate location of Retention Basin and areas on all sheets of Development Plan. Indicate fully dimensioned cross section details of retention basins & areas, and all drainage structures & pipes. Indicate a reference letter or number to indicate detail, WSE, viewing direction and dimensions to show what item is being view in location to the site. Location of proposed retention basin is unacceptable due to the MS&R future widening. Relocate retention basin. Indicate all elevations.

14. The following information shall be provided on the development plan drawing to indicate the existing conditions on site and within fifty (50) feet of the site. On sites bounded by a street with a width of fifty (50) feet or greater, the existing conditions across the street will be provided. Indicate structure/building footprints for adjacent properties. D.S. 2-05.2.3 Indicate on Sheet C-1.

15. For Sheet C-1, indicate the following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the right-of-way width for existing, future and widening (label each width as per type), label (existing and/or future) and dimensioned width of paving, curbs, curb cuts, and sidewalks. Indicate MS&R future widening width for Stone Ave. and Roger Road. D.S. 2-05.2.3. Indicate recordation data for Stone Ave.

16. Indicate the Datum that is being used on the site based on City of Tucson Datum. D.S. 2-05.2.3.E

17. Spot elevations shall be provided at all breaks in grade and along all drainage channels or swales and at selected points not more than one hundred (100) feet apart in all directions. D.S. 2-05.2.3.E.1 Indicate Top of Curb and Top of Pavement elevations along sidewalk/pathway from Roger Road, along retention areas by Stone Ave., along the northeast side PAAL and landscape area. Concrete cannot be flushed with asphalt unless it's a landing pad for refuse containers. Indicate grade breaks. Add grade break symbol to legend. Curb depth is six inches.

18. A symbol identical to that used to represent the water surface contour intervals on the development plan should be included in the legend. D.S. 2-05.2.3.I.3

19. Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. D.S. 2-05.2.4.D.2 As per MS&R map Stone Ave. and Roger Road are both MS&R roads, which intersect. Stone Ave.'s Future is 90' with a widening of 120', Roger Road's Future is 100' with a widening of 130'. Both streets have a 10 foot sidewalk area with a 6 foot sidewalk for the future. Indicate widening intersection as per MS&R Ordinance. D.S. 2-05.2.4.E Correct and revise all development plan sheets to indicate change.

20. Indicate existing, future and widening SVT's. The SVT's indicated on development plan are incorrect. SVT's for PAAL to Arterial streets (Stone Ave.) are; Near 345', Far 125', for PAAL to Collector streets (Roger Road) are; Near 265', Far 110'. Collector to Arterial are; Near 335', Far 125" and Arterial to Collector are; Near 245', Far 110'. Correct and revise. D.S. 3-01.5.3

21. If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, etc.) D.S. 2-05.2.4.F Indicate on all development plans.

22. Indicate and label radius for curb returns from Roger Road into PAAL.

23. Sidewalks within a project must be physically separated from any vehicular travel lane by means of curbing, grade separation, barriers, railings, or other means, except at crosswalks, and must meet the following locations requirements as per D.S. 2-08.4.1.A thru F.

24. A sidewalk will be provided adjacent and parallel to any PAAL on the side where buildings are located. D.S. 2-08.4.1.B & Figure 1

25. Dimension back-up spur areas as per D.S. 3-05.2.2.D & Figure 2

26. In conjunction with a drainage report or statement, as applicable, prepared in accordance with the City Engineer's instructions and procedures, the following information will be indicated on the development plan. For additional information regarding drainage standards, see the City of Tucson Standards Manual for Drainage Design and Floodplain Management. D.S. 2-05.2.4.H As per response to comment #30, "Not Applicable", all development over one acre and in a Non-designated basin are required to comply to D.S. 2-05.2.4.H

27. Show areas of Retention including 100-year ponding limits with water surface elevations. D.S. 2-05.2.4.H.1 In reference to Drainage Report, indicate all drainage structures and basin detail and information to development plan. Indicate basin bottom elevation and landscape areas.

28. Indicate proposed drainage solutions, such as origin, direction and destination of flow and method of collecting and containing flow. Indicate roof direction, drainage, downspouts and sidewalk scuppers. Indicate a dimensioned detail of downspout and scupper. D.S. 2-05.2.4.H.2

29. Indicate all proposed ground elevations at different points on each lot to provide reference to future grading and site drainage. Indicate symbol in legend. D.S. 2-05.2.4.H.4

30. Verification will be provided that any drainage solutions which occur outside the boundaries of the development plan area are constructed with adjacent owners' permission. (Additional notarized documentation of that approval will be submitted with the drainage report.) D.S. 2-05.2.4.H.5

31. For refuse collection trucks demonstrate vehicle maneuverability, fully dimensioned. Indicate a dimensioned detail of refuse enclosure as per D.S. 6-01.4.2.A thru D For specific information on refuse collection, refer to Development Standard 6-01.0. D.S. 2-05.2.4.T

32. The maximum back-up distance for the collection vehicle shall be forty feet. D.S. 6-04.4.1.C Sheet C-2 indicates an 85' backup before continuing its course. The collection vehicle cannot back up more than forty feet to continue the route and/or overlap (drive over) striped parking spaces and/or areas, loading zones or onto opposite lane in PAAL. Demonstrate vehicle maneuverability, fully dimensioned to indicate ingress, refuse location pickup and egress of site.

33. If applicable, indicate location and type of postal service to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping. D.S. 2-05.2.4.V As per response to comment #37, "Not applicable", all developments are applicable to D.S. 2-05.2.4.V Indicate a note that indicates proposed type of postal service.

34. Proposed sign monument is in the existing, future and widening right-of-way which is unacceptable. Relocate sign monument. Correct and revise.

35. Grading Plan is being view as a reference in comparison to the development plan for grading and drainage issues.

36. Proposed fills in excess of two feet above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property require the procedure outlined in IBC Chapter 36 Section 13.1. This process must be complete prior to Grading Plan approval. As per Sheet C-2 indicates the lowest existing grade of building footprint to be 2334.50 and the proposed finish floor elevation is 2335.00, which is a 3.5' difference. Correct and revise to indicate compliance to Chapter 36 Section 13.1. Indicate a dimensioned cross section detail of building indicating existing grade elevation, finished pad elevation and finished floor elevation. Indicate proposed elevations within building footprint on development plan.

Drainage Report
37. The development plan shall have a note stating (a) that the owner or owners shall be solely responsible for operation, maintenance, and liability for drainage structures and detention basins; (b) that the owner or owners shall have an Arizona Registered Professional Civil Engineer prepare a certified inspection report for the drainage and detention/retention facilities at least once each year. SMDDFM 14.3.2 Indicate statement in Drainage Report.

38. Indicate fully dimensioned details of all drainage structures, pipes, basins, and inlet/outlet structures in Drainage Report and Development Plan. Reference details according to location on plan.

39. Calculation for Retention basin indicates a lesser volume. The Cw dev factor as per SMDDFM 4.2.Table 4.3 & SDRM 3.2.Table 3.4 with 90% impervious surface is to be .85 for Soil B. Correct and revise.

40. Indicate Q100 inflows and outflows in basin areas on development plans.

41. A percolation test is required. SDRM 2.2
07/13/2004 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL


TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
D04-004
Family Dollar
3960 N. Stone Ave.
Development Plan

TRANSMITTAL: 7-13-04
DUE DATE: 7-14-04


1. Revise the location/vicinity map on sheet C-1 to include labeled section, township and range corners. Enlarge the text of the major street names in the location map and other text to be a minimum of 12 point (0.12") for microfilming.
DS 2-05.2.1.D
DS 2-05.2.1.C

2. Sidewalks within the project must be physically separated from vehicular travel lanes by means of curbing, except at crosswalks. It is difficult to determine from the line widths and variation in double and single lines where a vertical curb is proposed and where the pedestrian circulation system is flush to the pavement for crosswalks. Revise line work to be clearly defined and label curbs where proposed.
DS 2-08.4.1

3. A minimum 5-foot pedestrian refuge, including a 4-foot concrete sidewalk is required between the building and the PAAL. Please revise plan to show the 5-foot pedestrian refuge, fully dimensioned, along the north side of the building.
DS 3-05.2.2.B.1

4. In the loading zone calculation add the number of loading zones required and to be provided with each phase of development. Show the location of the second loading zone that will be required for future retail pad (see note 5 below).
DS 2-05.2.4.O

5. It is indicated that there is to be a space for future retail to the south of the proposed Family Dollar store. Provide a future plan for the second phase of development showing all calculations (FAR, vehicle parking, bicycle parking, loading zones, etc), setbacks, heights and dimensions to indicate that the future phase complies with all requirements separately. Future plan must show all future required parking and other requirements as to how the site will meet code in the future. Or, if a future plan is not to be provided at this time remove the area labeled "future retail space" as well as all notes and other references to "future retail space".
DS 2-05.2.5.C

6. The proposed freestanding monument sign along Roger Road is shown to be located within the SVT. Label the size and height of this sign on the plan. If it is to be higher than 30" above the at- grade centerline of the entrance drive from Roger Road, the sign must be located outside of the existing/future SVTs.
DS 3-01.5.1.A

7. Revise the math in the Floor Area Ratio (FAR) calculation to be correct and consistent (14.8% does not equal 0.178).
DS 2-05.2.4.M
DS 2-05.2.4.C

8. Provide the maximum slope of the handicap aisle and any associated ramps adjacent to the h/c vehicle parking spaces.
ANS

9. Please revise all figures on all sheets to be consistent. The square footage for the future building is stated to be 4,620 on the drawings but in the general notes it is stated to be 4,160 maximum.

10. It is indicated in first review response comment # 41 that the island at the south end of the parking lot is to be painted stripes on pavement only. The double line shown on the plan indicates a raised concrete curb is proposed. See comment 2 regarding consistency in line widths. If the proposal calls for striped pavement only, make all plans clear and consistent, including the landscape plan sheet L-1 and site development plan sheet C-1.

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

PSMc\H\Devplans04\D04-004rev2.doc

RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

PSMc\H\Devplans04\D04-004rev2.doc

RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.
07/13/2004 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP:

1. Ensure the monument sign located in the SVT meets the height spacing requirements

2. Curves C1, C4 are required to be 25' minimum

3. Label the radii at Roger Rd access point (25' minimum).

4. Stone Ave. is an arterial roadway. Near side SVT is 20x345, far side is 20x125.

5. Roger Rd. is a collector roadway. Near side SVT is 20x265, far side is 20x110.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
07/14/2004 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING AND DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D04-0004 Family Dollar Store/Stone 07/14/04

( ) Tentative Plat
( x ) Development Plan
( x ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: Annexation Ordinance #1895 and #1901

NEIGHBORHOOD PLAN: North Stone Neighborhood Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: July 12, 2004

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
( x ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( x ) Resubmittal Required:
( ) Tentative Plat
( x ) Development Plan
( x ) Landscape Plan
( x ) Other: Sign Package & Elevation Plan

REVIEWER: E. Anderson 791-4505 DATE: 07/12/04

COMPREHENSIVE PLANNING TASK FORCE
FAMILY DOLLAR/STONE, D04-004

The General Plan, North Stone Neighborhood Plan, Design Guidelines Manual and the Stone Avenue Corridor: Measures for a Livable Corridor all provide guidance for the review of this development.

1. The Stone Avenue Corridor: Measures for a Livable Corridor encourages street trees on the east side of Stone Avenue to be placed on both sides of the sidewalk. It also states that the trees should be at minimum 36-inch box size. In addition, it states that street trees should be selected from the plant palette for the Stone Avenue Corridor and that two feet deep root guards should be used if the roots could impact the sidewalk or street paving. To enhance the aesthetics of the corridor, staff continues to encourage the applicant to locate minimum 36-inch box size shade trees, from the plant palette, on both sides of the sidewalks (Roger and Stone). If necessary, please use the two feet deep root guards.

2. The Stone Avenue Corridor: Measures for a Livable Corridor encourages pedestrian nodes and shade-oriented bus shelters to be located at the same location. It also states that the pedestrian node should be landscaped with generous amounts of street trees, node trees, and accent shrubbery from the plant palette. In addition, it should have accent lighting to provide nighttime interest to the corridor and security lighting to give evening bus riders, and other pedestrians a sense of safety. To help create a more visually pleasing pedestrian node, staff continues to encourage the applicant to provide additional landscaping, including shade trees, and the appropriate lighting for the bus stops along Stone Avenue and Roger Road.

3. The Stone Avenue Corridor: Measures for a Livable Corridor states that buildings shall be constructed along the Stone Avenue street front and that parking should be located along the side or in the rear of the buildings. This is to increase access for pedestrians and visibility for drivers, and to create a greater feeling of sense of place. The Design Guidelines Manual states that new buildings should have similar setbacks as the prevailing setbacks in the neighborhood. To keep consistent with the existing setbacks along Stone Avenue, staff continues to encourage the applicant to reconfigure the lot layout and place the buildings closer to the Stone Avenue street front and locate the parking on the side and/or in the rear of the building.

4. The Stone Avenue Corridor: Measures for a Livable Corridor and the North Stone Neighborhood Plan state that design proposals for properties adjacent to Stone Avenue should demonstrate sensitivity to nearby neighborhoods. The Design Guidelines Manual states this should be done through four-sided architecture and detail comparable to the front façade, with consistent design treatment, including but not limited to, comparable color palette, signs, rooflines, and materials. To be sensitive to the surrounding uses and zoning districts, and to help promote further neighborhood reinvestment, staff continues to encourage the applicant to design side and rear building façades with attention to architectural character and detail comparable to the front façade. Please submit color elevations of all four sides of the proposed building.

5. The North Stone Neighborhood Plan states that the architectural features of proposed structures should be enhanced and softened using drought tolerant vegetation proportional in scale and mass to architectural element. This includes trees, shrubs, and groundcover. To be sensitive to the surrounding uses, staff continues to encourage the applicant to provide trees, shrubs, and groundcover, from the plant palette, along the sides of the proposed building.

6. The Design Guidelines Manual and North Stone Neighborhood Plan both state that dumpsters shall be screened with masonry walls and landscaping. The Design Guidelines Manual states that the screen around dumpsters shall consist of material such as tile, stone, or brick and plantings up to six feet high. It also states that the screen walls should be constructed with graffiti-resistant materials and encourages shared dumpsters. Staff continues to encourage the applicant to provide a graffiti-resistant tile, stone, or brick masonry screen wall around all dumpster locations and plantings up to six-feet high next to the wall. Also, please show where the dumpster will be located after the future retail building is constructed.

7. The General Plan, North Stone Neighborhood Plan, and Design Guidelines Manual state that loading zones and dumpsters should be kept away from residential parcels and zoning. To be sensitive to surrounding properties, staff continues to encourage the applicant to locate the proposed loading zone a minimum of fifty feet from the R-2 zoning district lines.

8. The Design Guidelines Manual states that the impact of freestanding walls over 75 feet long and over three feet high should be reduced. Staff continues to encourage the applicant to construct all required or proposed masonry walls with graffiti-resistant paint or materials. Please incorporate two or more visually appealing design treatments, such as; the use of two or more decorative materials like stucco, tile, or brick; a visually interesting design on the wall surface; varied wall alignments; and/or trees and shrubbery in voids created be wall variations.

9. The Design Guidelines Manual, General Plan, and North Stone Neighborhood Plan encourage temporary vacant areas within a development to be landscaped with a minimum of decomposed granite and ground vegetation. To control dust and to visually enhance an area that could stay vacant, staff continues to encourage the applicant to locate appropriate vegetation in the area that is designated as "space for future retail".

10. The Design Guidelines Manual states that the use of vegetation should be used in parking areas to reduce heat build-up. Staff continues to encourage the applicant to provide additional vegetation islands, which include shade trees, within the parking areas. This could be done with an additional vegetation island in the main parking area.

11. The General Plan and Design Guidelines Manual state that signs should be incorporated with and improve the aesthetics of a development. Both also have policies that promote signage that is clear, but is not the dominant feature of the development. To ensure compatibility with the plans and to ensure sensitivity to the surrounding area, staff continues to encourage the applicant to provide the desired sign package, which follows the applicable plans, for the proposed use.
07/16/2004 CRAIG GROSS ZONING-DECISION LETTER REVIEW Completed
07/16/2004 CRAIG GROSS PIMA COUNTY WASTEWATER Approv-Cond July 16, 2004

TO: Irene Volenick, Planning Resources

THRU:


FROM: ____________________________________
representing the Pima County
Departments of Wastewater Management and Environmental Quality

SUBJECT: Family Dollar Store - Stone Avenue
- Submittal
D04-0004


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET C-0. Include the following four General Notes

ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT AT THE TIME OF SUBMITTAL OF PLUMBING OR BUILDING PLANS.

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

ANY WASTEWATER DISCHARGED INTO THE PUBLIC SANITARY SEWERAGE SYSTEM SHALL MEET THE REQUIREMENTS OF THE INDUSTRIAL WASTE ORGINANCE (PIMA COUNTY ORDINANCE NO. 1991-140, AS AMENDED).

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

SHEET C-3. Show the Pima County plan number on the existing sewer line(s). While the existing manhole numbers and their information is shown, the Pima County plan number must be shown.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you wish to discuss the above comments, please contact me at the phone number provided above, under my signature.

Copy: Project