Plan Number: TW-WCP-1223-00125
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Requires Resubmit

Review Details: WATER DESIGN PLAN REVIEW v.1

Plan Number - TW-WCP-1223-00125
Review Name: WATER DESIGN PLAN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
TFD Review & Signature PENDING ASSIGNMENT
TW Design Plan Review PENDING ASSIGNMENT
TW Issue Invoice PENDING ASSIGNMENT
TW Managerial Review PENDING ASSIGNMENT
TW Verify Fees Paid PENDING ASSIGNMENT
TW Administrative Completeness REQUIRES RESUBMIT Your submittal is incomplete.
Item 6 of the Checklist: Improvement and landscape plans are missing from the submittal.

Item 7 of the Checklist: Underground electric Layout missing from the submittal.

Master Plan redline comments were not addressed on the Design plan: Tucson Water-New Development Format Standard Title Block was not used. Coversheet does not meet the drafting standards. Offsite Design for the existing 10-inch main replacement as per master plan comments was missing from plan.

Control information that ties the control lines on the project to existing monumentation is missing from the plan. Vertical Scale is incorrect for all profiles (1"=2' is required for 20 scale hz). Rolling tees are not permitted. 2-inch valves for services are not permitted.

Design and drafting standards are not being met throughout the design.

Tucson Water requests a meeting to discuss prior to the first official design submittal.