Permit Number: TS-PRM-1125-00486
Parcel: 125121110

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.2

Permit Number - TS-PRM-1125-00486
Review Name: PERMANENT SIGN REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TS-PRM-1125-00486 (3400 E SPEEDWAY BL Unit:UNIT 108 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Add the following verbiage to each internally illuminated sing sheets.

All Signs and power supply components are UL listed. NEC 600.3.
All Signs shall have UL sticker, manufacturer sticker & Installer sticker, located on the exterior of the sign. NEC 600.4.
All dedicated sign circuits shall be labeled. NEC 600.5.
A safety lockout shall be provided for all signs where the shut off switch is not directly visible to the sign. NEC 600.6.

This sign is intended to be installed in accordance with the requirements of Article 600 of the 2017 National Electrical Code and/or other applicable codes. This includes proper grounding and bonding of the sign, Article 600.7 and location of the disconnect switch after the installation shall comply with Article 605(A)(1) of the National Electrical Code.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/09/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TS-PRM-1125-00486 (3400 E SPEEDWAY BL Unit:UNIT 108 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Add the following notes to each Internally Illuminated Sigh sheet:

“As per the City of Tucson Outdoor Lighting Code – The internally illuminated sign shown on this page does not exceed the color temperature of 4400K, OLC 501.3.2.”
12/26/2025 Signs Standard REQUIRES RESUBMIT Sign Review TS-PRM-1125-00486 3400 E. Speedway Bl. #108. Plan review for the above referenced structure has been completed by Tami Goltz. This letter reflects comments to be addressed. Additional comments may be provided in subsequent reviews. Code reference: Unified Development Code, Article 7A: Sign Standards, adopted Outdoor Lighting Code, adopted Building Code. Please feel free to reach out with any questions you may have. Tami.Goltz@tucsonaz.gov or 520-837-5049.
1) The following exact copy is required to be added to the drawings:
⦁ All signs and power supply components are UL listed.
⦁ All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.
⦁ All dedicated sign circuits shall be labeled.
⦁ A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign
⦁ 24 hour programmable timer installed to comply with the COT Outdoor Lighting Code
⦁ As per the City of Tucson Outdoor Lighting Code the internally illuminated sign as shown on this page does not exceed the 4400k color temp.
2) Specify exact materials the wall is constructed of. Include all materials, not just finishing materials like EIFS or stucco.
3) Provide type, size and number of butterfly anchors to be used in attachment of sign to wall.
4) Outline tenant space within building and indicate frontage amount on site plan.
5) Provide City of Tucson business license on application. If one does not exist, contact the business license department to obtain one.