Permit Number: TS-PRM-0923-00492
Parcel: 11504480A

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0923-00492
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2023 Signs REQUIRES RESUBMIT RE: sign review
For: wall signs, change copy on freestanding sign, new menu board – option new monument
AT: The Pacific (Apartments – high rise), 1020 N Tyndall Av
Sign permit: TS-PRM-0923-00492
Reviewer: H. Thrall
Date: 09/20/23

Codes: Unified Development Code (UDC), 7A Sign Standards, National Electrical Code (NEC), Tucson- Pima County Outdoor Lighting Code (OLC), International Building Code (IBC) 2018

1. UDC:
A) I acknowledge the sign area variance from 2014 for the increased sign area above 50 square feet for apartment uses, to be placed on the south elevation. The changed wall sign plan would allow this increase to the proposed approximately 65 square foot wall sign on that same south elevation.
B) Per 7A.10.2.B chart – the “U” zoning of the location requires that the Main Gate UOD overlay is reviewed for signs over 50 square feet in area. As such, the plans will need to be forwarded for that review process once the required notes and engineered plans are submitted.
2. NEC:
A) Add note: “lock out to be provided due to location of shut off switch to sign”
B) Add note; “dedicated sign circuit shall be provided and labeled at breaker panel, to be shown at inspection”
C) Add note: “UL, Manufacturer and Installer sticker to be provided on side of sign”
D) Add note: “sign and all components shall be UL or equivalent and outdoor rated”

3. OLC: no comments, thank you
4.` IBC:
A) engineered plans required for mounting
B) special inspection required for mounting and height off the ground

Depending on responses provided, further review comments may be forthcoming. I may be reached via email at Heather.Thrall@tucsonaz.gov