Permit Number: TS-PRM-0625-00259
Parcel: 11007414H

Address:
3997 E GRANT RD

Review Status: Requires Resubmit

Review Details: PERMANENT SIGN REVIEW v.1

Permit Number - TS-PRM-0625-00259
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2025 Commercial Electrical Fast APPROVED
06/24/2025 Outdoor Lighting Standard APPROVED
06/24/2025 Signs Standard REQUIRES RESUBMIT Application:
1) We can not approve this permit until the building permit TC-COM-0625-001177 is paid for and issued. Resubmit once the building permit is paid for and issued.

Sign Drawings:
1) Add Required Exact Copy:
All signs and power supply components are UL listed.

All signs shall have UL sticker, manufacturer sticker and installer sticker, located on the exterior of the sign for inspections.

All dedicated sign circuits shall be labeled.

A safety lock out shall be provided for all signs where the shut off switch is not directly visible to the sign.

2) Provide a call out for what materials the wall is made from. I.E. Masonry, Wood with stucco, etc...

3) Specify the anchors that are used to hold the sign to the wall.

4) Add the number of AMPs this sign will pull when illuminated.