Permit Review Detail
Review Status: Requires Resubmit
Review Details: PERMANENT SIGN REVIEW v.1
Permit Number - TS-PRM-0526-00174
Review Name: PERMANENT SIGN REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2026 | Commercial Building Standard | APPROVED | |||
| 05/18/2026 | Commercial Electrical Fast | APPROVED | |||
| 05/18/2026 | Outdoor Lighting Standard | APPROVED | |||
| 05/20/2026 | Design Review Standard | NOT REQUIRED | No Rio Nuevo Area (RNA) review is required, since proposed signs are not changing the architectural design of the building. | ||
| 06/09/2026 | Signs Standard | REQUIRES RESUBMIT | FROM: Georgia Pennington DATE: 6/8/26 COMMENTS: 1. The proposed wall signs exceed the maximum allowed sign area for a multifamily use. Multifamily uses are allowed a maximum sign area of 50 square feet. The submitted plans propose two 35 square foot wall signs, for a total of 70 square feet. Revise the plans so the total proposed sign area does not exceed 50 square feet. If additional sign area is needed beyond the allowed 50 square feet, the applicant may apply for a Master Sign Program (MSP) as a separate application. Approval of an MSP is not guaranteed and must be reviewed under the applicable UDC Section 7A standards. If you have questions, or if you would like to start the Master Sign Program process, please contact Georgia Pennington at georgia.pennington@tucsonaz.gov. |
||
| 05/18/2026 | Signs Application Completeness Express | REVIEW COMPLETED |