Permit Number: TF-FCP-1225-01017
Parcel: 11506107B

Address:
1910 N STONE AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1225-01017
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2026 Fire New Construction - Standard REQUIRES RESUBMIT Provide standpipe isolation valves, NFPA 14, 9.6.2 Provide the RFI regarding insulation, See details sheet A500 of const. documents. Update code references to meet requirements of 2024 IFC Provide sprinklers in closets in accordance with NFPA 13, 9.5.5.4 Connect piping or provide proof calc at level 4 and update nodes Verify roof top hose valve. Review additional notes on plans. Questions: patricia.shelton@tucsonaz.gov
01/28/2026 TFD Application Completeness Check Express REVIEW COMPLETED