Review Status: Approved
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-1225-01017
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2025 | Fire New Construction - Standard | REVIEW COMPLETED | Provide standpipe isolation valves, NFPA 14, 9.6.2 Provide the RFI regarding insulation, See details sheet A500 of const. documents. Update code references to meet requirements of 2024 IFC Provide sprinklers in closets in accordance with NFPA 13, 9.5.5.4 Connect piping or provide proof calc at level 4 and update nodes Verify roof top hose valve. Review additional notes on plans. Questions: patricia.shelton@tucsonaz.gov |
||
| 12/09/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |