8700 E KENYON DR

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1223-01460
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2024 Fire New Construction REQUIRES RESUBMIT These plans reference both NFPA 13D and NFPA 13R. It appears the preferred is NFPA 13R? If this is the case, it appears your connection is off the existing 5/8" meter? Tucson Water requires a min. 1½" meter for flows above 50gpm and less than 100gpm.

An NFPA 13R system is required to have a 2½" FDC and a Fire Alarm (I assume by others).

Please clarify the scope of work, i.e. 13D or 13R, new tap to city water, use of existing meter, etc.