Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1223-01460
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2024 | Fire New Construction | REQUIRES RESUBMIT | These plans reference both NFPA 13D and NFPA 13R. It appears the preferred is NFPA 13R? If this is the case, it appears your connection is off the existing 5/8" meter? Tucson Water requires a min. 1½" meter for flows above 50gpm and less than 100gpm. An NFPA 13R system is required to have a 2½" FDC and a Fire Alarm (I assume by others). Please clarify the scope of work, i.e. 13D or 13R, new tap to city water, use of existing meter, etc. |
||
| 01/08/2024 | TFD Application Completeness Check Express | REVIEW COMPLETED |