Permit: TF-FCP-1223-01460
Permit Details
Status:
Expired
Type:
Fire Construction Permit
Address:
8700 E KENYON DR
Address NEW:
8700 E KENYON DR
Apply Date:
12/29/2023
Applicant:
Elisa Novelo
Description:
INSTALL NEW FIRE SPRINKLER SYSTEM TO AN EXISTING RESIDENTS.
Permit Reviews
Permit Number - TF-FCP-1223-01460
Permit Status: Expired
Permit Description: INSTALL NEW FIRE SPRINKLER SYSTEM TO AN EXISTING RESIDENTS.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/29/2024 | FIRE CONSTRUCTION REVIEW v.3 | 02/01/2024 | REQUIRES RESUBMIT |
| 02/08/2024 | FIRE CONSTRUCTION REVIEW v.4 | 03/05/2024 | APPROVED |
| 01/08/2024 | FIRE CONSTRUCTION REVIEW v.2 | 01/16/2024 | REQUIRES RESUBMIT |
| 01/02/2024 | FIRE CONSTRUCTION REVIEW v.1 | 01/02/2024 | REQUIRES RESUBMIT |
Outstanding Inspections
Permit Status: Expired
Permit Number: TF-FCP-1223-01460
Permite Description: INSTALL NEW FIRE SPRINKLER SYSTEM TO AN EXISTING RESIDENTS.
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2025 | COT - FCON - Sprinkler - Final | N/A | Re-inspection required | The water meter is not the right size. The plans call for an 1 1/2" but there is only an 1" installed, there are two valves installed on the water supply before the riser shall be removed, the system need to have the 200 lbs hydro test and inspection. |