Permit Number: TF-FCP-1222-00223
Parcel: 13727012E

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1222-00223
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2023 Fire New Construction REQUIRES RESUBMIT Notes show that you are installing 1 back flow preventor for all risers shown on plan, however you are only showing 1 building riser calculation. It is not noted that the system calculation provided is for the most demanding system.
Plans do not show a check valve at the F.D.C. nor a means for providing a full forward flow test.
Provide cut sheets for the system and or chemical being deployed.
Provide cut sheet for the back flow preventor being installed.
Is the system deployed permanent and or removeable? If removeable please note the frequency of the chemical being reintroduced into the system(s)
Plans note that the system is an Ordinary Hazard Group II with a .1 density (Light hazard) please correct.

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
12/20/2022 TFD Application Completeness Check REVIEW COMPLETED