Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TF-FCP-1126-00709
Parcel: 14043013B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1126-00709
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please resubmit with required voltage drop calculations and back up battery calculations showing existing equipment and new equipment can be sufficiently powered by the existing battery or upgrade battery to supply entire system (existing and new).
For questions of concerns on this, please reach out to me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(c) 520 539-5370
Ryan.Johnson@Tucsonaz.gov
11/10/2026 TFD Application Completeness Check Express REVIEW COMPLETED