Permit Number: TF-FCP-1124-00923
Parcel: 126191910

Address:
4431 E 22ND ST

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1124-00923
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2024 Fire New Construction REQUIRES RESUBMIT Please protect hydraulic elevators (9.3.6.1)

Provide coverage at trash chute (IFC 903.2.11.2)

Provide coverage at closets (TFD has not adopted NFPA 101 to make this omission acceptable)

There are multiple units with heads spaced more than 9'-0" off the wall, this exceeds the calculated coverage.

There are also areas of the soffit that are over 24" and will require spacing in accordance with NFPA 13, 12.1.10.1.2.

Please provide approved architectural detail showing combustible concealed space filled with insulation, this does not match the detail on the permit drawings.

Please verify calculations work with revised information (Sheet FP1). Original flow data was obtained from the main in 22nd St. The revised data is provided for the main the underground will connect to.

Please let me know if you have any questions, or if I missed a revision to the code that would permit any of these.