Permit Number: TF-FCP-1124-00922
Parcel: 14042025A

Address:
2713 E CORONA RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1124-00922
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2024 Fire New Construction REQUIRES RESUBMIT System static pressure is 183.150 psi, sprinkler heads are only rated for 175psi, please correct this.
Also the test header needs to be sized in accordance with NFPA 20, 2022, 4.28