Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1124-00922
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/27/2024 | Fire New Construction | REQUIRES RESUBMIT | System static pressure is 183.150 psi, sprinkler heads are only rated for 175psi, please correct this. Also the test header needs to be sized in accordance with NFPA 20, 2022, 4.28 Questions: patricia.shelton@tucsonaz.gov |
||
| 12/16/2024 | TFD Application Completeness Check Express | REVIEW COMPLETED |