Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-1026-00668
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | On plan page FA-05, Battery calculation for NACPS #1 calcs out to require a minimum 11.069Ah battery for backup functionality. Plans provide for only a 7Ah backup battery. Please adjust this to provide at least the required minimum battery capacity. | ||
| 10/22/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |