10/30/2026 Fire New Construction - Standard REQUIRES RESUBMIT On plan page FA-05, Battery calculation for NACPS #1 calcs out to require a minimum 11.069Ah battery for backup functionality. Plans provide for only a 7Ah backup battery. Please adjust this to provide at least the required minimum battery capacity.