Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0926-00580
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please provide the following missing information: - Diameter, type, and length of all segments (4.1.3) - Indicate method and type of joint restraints (4.1.3) - Note indicating fire service underground to conform to NFPA 24 - Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2) - Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1) Questions: patricia.shelton@tucsonaz.gov |
||