Permit Number: TF-FCP-0926-00580
Parcel: 140410070

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0926-00580
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please provide the following missing information:
- Diameter, type, and length of all segments (4.1.3)
- Indicate method and type of joint restraints (4.1.3)
- Note indicating fire service underground to conform to NFPA 24
- Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2)
- Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1)
Questions: patricia.shelton@tucsonaz.gov
10/20/2026 TFD Application Completeness Check Express REVIEW COMPLETED