Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0426-00268
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please provide statement that existing system meets the requirements of the 2024 IFC, 1103.1. Stating the current building protected by the fire alarm is up to the code requirements of the 2024 IFC.
Also, please reference plan set as devices do not match previous permits (applied for and completed by Climatec). There was also a completed permit for the installation of a cell dialer, by Climatec.
Questions: patricia.shelton@tucsonaz.gov
05/05/2026 TFD Application Completeness Check Express REVIEW COMPLETED