Permit Details

Status:
Complete
Type:
Fire Construction Permit
Apply Date:
04/27/2026
Applicant:
Bosch Building Technologies Office
Description:
PROVIDE AND INSTALL REQUIRED FIRE LIFE SAFETY DEVICES FOR THE CONTINUED PROTECTION AT BOSCH TUCSON. DEVICES LOCATED OUTSIDE THE SCOPE OF WORK ARE EXISTING AND TO REMAIN UNCHANGED. THE EXISTING PANEL WILL BE REPLACED WITH A NEW EDWARDS EDGE PANEL. ALL EXISTING FIELD DEVICES WILL REMAIN UNCHANGED. THE EXISTING PHONE LINES WILL BE RE-USED FOR MONITORING.

Permit Reviews

Permit Number - TF-FCP-0426-00268
Permit Status: Complete
Permit Description: PROVIDE AND INSTALL REQUIRED FIRE LIFE SAFETY DEVICES FOR THE CONTINUED PROTECTION AT BOSCH TUCSON. DEVICES LOCATED OUTSIDE THE SCOPE OF WORK ARE EXISTING AND TO REMAIN UNCHANGED. THE EXISTING PANEL WILL BE REPLACED WITH A NEW EDWARDS EDGE PANEL. ALL EXISTING FIELD DEVICES WILL REMAIN UNCHANGED. THE EXISTING PHONE LINES WILL BE RE-USED FOR MONITORING.
Start Date Submittal Complete Date Status  
06/22/2026 FIRE CONSTRUCTION REVIEW v.2 07/16/2026 APPROVED Review Details
05/05/2026 FIRE CONSTRUCTION REVIEW v.1 05/27/2026 REQUIRES RESUBMIT Review Details

Outstanding Inspections

Permit Status: Complete
Permit Number: TF-FCP-0426-00268
Permite Description: PROVIDE AND INSTALL REQUIRED FIRE LIFE SAFETY DEVICES FOR THE CONTINUED PROTECTION AT BOSCH TUCSON. DEVICES LOCATED OUTSIDE THE SCOPE OF WORK ARE EXISTING AND TO REMAIN UNCHANGED. THE EXISTING PANEL WILL BE REPLACED WITH A NEW EDWARDS EDGE PANEL. ALL EXISTING FIELD DEVICES WILL REMAIN UNCHANGED. THE EXISTING PHONE LINES WILL BE RE-USED FOR MONITORING.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
COT - FCON - Alarm - Final N/A Not Ready Need to connect Tamper Switch to FACP.
Need to reprogram Water Flow signal to General Alarm versus supervisory.

Completed Inspections

Permit Status: Complete
Permit Number: TF-FCP-0426-00268
Permit Description: PROVIDE AND INSTALL REQUIRED FIRE LIFE SAFETY DEVICES FOR THE CONTINUED PROTECTION AT BOSCH TUCSON. DEVICES LOCATED OUTSIDE THE SCOPE OF WORK ARE EXISTING AND TO REMAIN UNCHANGED. THE EXISTING PANEL WILL BE REPLACED WITH A NEW EDWARDS EDGE PANEL. ALL EXISTING FIELD DEVICES WILL REMAIN UNCHANGED. THE EXISTING PHONE LINES WILL BE RE-USED FOR MONITORING.
Total Completed Inspections - 1
Date Description Inspector Results Comments
10/06/2026 COT - FCON - Alarm - Final Passed

Documents

File Name Document Type  
BOSCH BT SUBMITTAL_V1.PDF DOCUMENTS VIEW
BOSCH BT SUBMITTAL_V1_V2.PDF DOCUMENTS VIEW
BOSCH TUCSON PANEL REPLACEMENT FA DRAWING R2_V2.PDF DOCUMENTS VIEW
BOSCH TUCSON PANEL REPLACEMENT FA DRAWINGS R2_V1.PDF DOCUMENTS VIEW