Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0425-00331
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | 907.1.2 Fire alarm shop drawings. (IFC 2024) Shop drawings for fire alarm systems shall be prepared in accordance with NFPA 72 and submitted for review and approval prior to system installation. 1. Per NFPA72: Install-Keep smoke detection at Living room-Sofa area with the required sounder base. 2. Mark with a cloud all the smoke detectors and sounder bases that are required by NFPA72 Section 29.8.1.1 for clarification and field inspections. The adopted City of Tucson Fire Code is the 2024 IFC with local amendments, The NFPA72 edition is 2022 check requirements and make appropriate corrections. |
||
| 04/24/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |