Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0326-00164
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Conflicting notes on plans regarding structure. It appears to be comb. obstructed, as stated on sheet FP1, but design and notes on other sheets imply non-comb., unobstructed. This would affect spacing, as well as lack of coverage at second floor patios. Please label full height walls. Questions: patricia.shelton@tucsonaz.gov |
||