Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0225-00163
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | The Underground Fire Line Plan should include the following (at a minimum): - Physical address of the project (4.1.3) - Point of compass (4.1.3) - Drawn to scale (4.1.3) - Size and location of all water supplies (4.1.3) - Installing contractor, including address, phone number and ROC information (4.1.3) - Diameter, type, and length of all segments (4.1.3) - Indicate method and type of joint restraints (4.1.3) - Indicate location and type of all valves on the fire service underground (4.1.3) - Note indicating fire service underground to conform to NFPA 24 - Note minimum depth of bury to be _______. (30”, more if under high-weight traffic) (4.1.3) (10.4.2.2.2) - Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2) - Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1) - Provide a Contractors Material and test Certificate for Underground Pipping as required by NFPA 13 2022 section 6.10.11 (at inspection) Questions: patricia.shelton@tucsonaz.gov |
||
| 02/26/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |