Permit Number: TF-FCP-0224-00116
Parcel: 14039052F

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0224-00116
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2024 Fire New Construction REQUIRES RESUBMIT Plans must indicate the following:
The Site Plan should include the following:
- Actual physical address of project
- Installing contractor, including address, phone number and ROC information
- Diameter, type, and length of all segments
- Indicate method and type of joint restraints
- Note indicating fire service underground to conform to NFPA 24
- Note minimum depth of bury to be _______. (typically 30”, more if under high weight traffic)
*per NFPA 24 2016ed. 10.4.2.2.2.
- Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours
*per NFPA 24 2016ed. 10.4.2.2.1.
- Note system to be flushed, and flush witnessed by TFD inspector
*per NFPA 24 2016ed. 10.10.1.
Please note inspectors will be looking at tracer wire, poly wrap of metallic fittings, etc at time of hydro.
Questions: patricia.shelton@tucsonaz.gov
02/27/2024 TFD Application Completeness Check REVIEW COMPLETED