Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW v.2
Permit Number - TD-DEV-1224-00333
Review Name: DEVELOPMENT PACKAGE NEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/05/2025 | Commercial Plumbing | APPROVED | |||
02/19/2025 | NPPO | APPROVED | |||
02/26/2025 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
02/07/2025 | Site Engineering | REQUIRES RESUBMIT | 1. Provide a drainage report that shows first flush retention and balanced basin detention compliance with sections 2 and 3 of The Design Standards for Stormwater Detention and Retention (DSSDR). 2. The waste enclosure cannot be located where the gates would open onto pedestrian circulation and where service vehicles would not be able to drive directly to the dumpsters for collection. Relocate the enclosure where it can be directly accessed from the PAAL. Provide waste stream calculations per TSM 8 using warehouse waste generation rates. Provide details of the waste enclosure and show compliance with TSM 8. 3. Detail G on sheet 7 shows a cross slope of 4.9% along the direction of travel for pedestrians, right where the ADA parking spaces are located. The maximum cross slope for ADA compliance is 2%. Please revise. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
02/19/2025 | Site Landscape | REQUIRES RESUBMIT | CDRC TRANSMITTAL PLANNING AND DEVELOPMENT SERVICES DEPARTMENT REVIEWER: CHAD KELLER, RLA SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION PROJECT: YOURSPACE SELF STORAGE DEVELOPMENT PACKAGE ACTIVITY NO: TD-DEV-1224-00333 ADDRESS: 980 W IRVINGTON RD ZONING: C-2 COMMERCIAL ZONE This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting. Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape/NPPO Section review comments have been addressed. SITE LANDSCAPE/NPPO SECTION COMMENTS: 1. Add the landscape plan set to the overall development package for the next submittal so that the plans can be approved as one compiled set. 2. Add reference callouts to the civil plans for the new 5’ masonry screen wall detailing. 3. Can landscape note number 10 on sheet 16 of 20 (dust control) reference the rock materials note with regard to screened rock? Possibly note the screened rock that is spec’d under rock materials note instead of decomposed granite. 4. Your elevation callouts at the bottom of the WHIA, inlets and outlets are perfect. Add a bold general note to the CRWHP sheet 22 of 26 that refers to the civil grading plans for all detailed drainage and basin construction including slopes, spot elevations, contouring, curb cuts, downspouts, splash pads, erosion control measures, etc. 5. Can a wall mounted controller detail be added to the set? 6. Provide the development package case number, TD-DEV-1224-00333, adjacent to the title block on all sheets. 2-06.4.3 7. Prior to Site Landscape Development Package approval, please make sure Site Zoning and Site Engineering comments are addressed. Thank you. Chad Keller, RLA Landscape Architect chad.keller@tucsonaz.gov 520.837.4923 |
||
02/10/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Yourspace Self Storage Development Package (1st Review) TD-DEV-1224-00333 TRANSMITTAL DATE: February 10, 2025 DUE DATE: February 7, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 16, 2026. 2-06.3.0 FORMAT REQUIREMENTS 1. COMMENT: 2-06.3.12 – The sheet index shows 26 sheets but only 13 were submitted. 2-06.4.0 CONTENT REQUIREMENTS 2. COMMENT: 2-06.4.2.D – The total number of sheets shown on the plans is 26 but only 13 were submitted. 3. COMMENT: 2-06.4.3 – Provide the development package case number, TD-DEV-1224-00333, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 4. COMMENT: 2-06.4.7.A.6.a – The UDC Articles for the Major Streets and Routes listed under Zoning and Land Use Note 6 is not correct. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 5. COMMENT: 2-06.4.8.B – The “16.0’ EX ELECTRICAL ESMT TO BE ABANDONED” will need to be abandoned prior to approval of this DP. Zoning acknowledges that the plans show a “16.0’ EX ELECTRICAL ESMT TO BE ABANDONED BY SEPARATE INSTRUMENT PRIOR TO CERTIFICATE OF OCCUPANSY ISSUED FOR BUILDING”, but as there are no building plans if review for this site Zoning cannot put a hold on the C of O. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 6. COMMENT: 2-06.4.9.H.5.d – The short-term bicycle parking detail does not address UDC Articles 7.4.9.B.1.a, .e, & 7.4.9.B.2 .f. 7. COMMENT: 2-06.4.9.o – As the code is not clear after discussion with staff, Elisa Hamblin Zoning Administrator, the provide perimeter yard setback listed for Interstate 19 is not correct and should be listed as 10’-0”. 8. COMMENT: 2-06.4.9.U – Rezoning condition 6 was not addressed correctly. Provide a copy of the required recorded cross-access agreement with the next submittal. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf. |
||
01/21/2025 | CDRC Review Coordinator Express | REVIEW COMPLETED | CDRC added ADOT, TEP PAG, USPS, SWG to the workflow. Review request email sent to ADOT and TEP. FYI email sent to PAG, USPS, SWG. | ||
02/26/2025 | External Reviewers - Arizona Department of Transportation (ADOT) Standard | REVIEW COMPLETED | Good Afternoon, ADOT has no comments on this DEV. Thank you for the opportunity to review. |
||
01/21/2025 | External Reviewers - Pima Association of Governments Standard | REVIEW COMPLETED | CDRC added ADOT, TEP PAG, USPS, SWG to the workflow. Review request email sent to ADOT and TEP. FYI email sent to PAG, USPS, SWG. | ||
01/21/2025 | External Reviewers - Southwest Gas Standard | REVIEW COMPLETED | CDRC added ADOT, TEP PAG, USPS, SWG to the workflow. Review request email sent to ADOT and TEP. FYI email sent to PAG, USPS, SWG. | ||
02/21/2025 | External Reviewers - Tucson Electric Power (TEP) Standard | REVIEW COMPLETED | February 20, 2025 WO#T140078 City of Tucson Planning and Development Services Attn: CDRC Admin Team Dear CDRC Admin Team Subject: Yourspace Self Storage TD-DEV-1224-003333 Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted 1/22/2025. There are existing facilities within the development which are depicted upon the plan; at this time there are no apparent conflicts. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. To apply for electric service, please call the New Construction department at (520) 918- 8300. Please submit a final set of plans including approved site, electric load, paving off-site improvements and irrigation plans. If available, include a PDF version of the plans. If easements are required, they will be secured by separate instrument. Should you have any easement questions, please contact our Land Resources Department, LandReviews@tep.com. Should you have any technical questions, please contact the area designer, Fred Quintero (520) 235-6329 fquintero@tep.com Sincerely, Design Admins Design Admins Tucson Electric Power |
||
01/21/2025 | External Reviewers - United States Postal Service (USPS) Standard | REVIEW COMPLETED | CDRC added ADOT, TEP PAG, USPS, SWG to the workflow. Review request email sent to ADOT and TEP. FYI email sent to PAG, USPS, SWG. | ||
02/05/2025 | Fire New Construction | REVIEW COMPLETED | TD-DEV-1224-00333. 2024 International Fire Code Requirements for proposed project: 2024 IFC Section 903.2.9: S-1 Occupancy requires an Automatic Fire Sprinklers System. 2024 IFC Section 907.2.10.1 S-1 occupancy requires a Fire Alarm System. 2024 IFC Section 510, requires an Emergency Responders Communications Enhancement System. (Testing to see if needed) 2024 IFC, Appendix D requires an Aerial Apparatus Access Road. The 4 fire hydrants showing in the plans are sufficient for the project. If you need additional information, please contact me at sal.erivezjr@tucsonaz.gov |
||
01/17/2025 | OK to Submit - Zoning Fast | REVIEW COMPLETED | |||
01/21/2025 | ROW Engineering Review | REVIEW COMPLETED |