Permit Number: TD-DEV-0924-00258
Parcel: 30501005A

Address:
10000 S RITA RD

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0924-00258
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2024 CDRC Post Review Express PENDING ASSIGNMENT
10/25/2024 NPPO REQUIRES RESUBMIT Please see Site Landscape Comments.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
10/21/2024 Site Engineering REQUIRES RESUBMIT 1. The SWPPP shows the "Containment Area" which includes the concrete washout area located outside of the construction site and perimeter control measure. Please locate this within the construction site, or provide additional perimeter control around this area.
2. Table 3-3 of the drainage report shows a value of 140 for the Table 2.1 multiplier for both disturbed and impervious area. Please revise using 1440 for impervious area.
3. On Table 3-6 in the drainage report, the units for infiltration rate are not clear. Please clarify.

Mike Ortiz
michael.ortiz@tucsonaz.gov
10/25/2024 Site Landscape REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
PDSD SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: RESTRICED ACCESS - TEP ROADRUNNER RESERVE 2 BESS
ACTIVITY NO: TD-DEV-0924-00258
ADDRESS: 10000 S RITA RD
ZONING: RH RURAL HOMESTEAD ZONE

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all Landscape/NPPO Review Section comments are addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

2. Provide the development package case number, TD-DEV-0924-00258, adjacent to the title block on all sheets. 2-06.4.3

3. Update the NPPO sheet number from G-1 to N-1.

4. Add the detail #1 to sheet G-1 that is reference in the Native Plant Preservation and Salvage Notes.

5. Remove the preliminary not for construction note over the registrant’s seal. Sign and date the plans prior to site landscape/nppo section approval.

6. Are there plans to revegetate the grading disturbance or the basin area? If so, provide a planting and irrigation plan and pertinent details.

If you have any questions about these comments, I can be reached at chad.keller@tucsonaz.gov
10/18/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Roadrunner Reserve II
Development Package (1st Review)
TD-DEV-0924-00258

TRANSMITTAL DATE: October 18, 2024

DUE DATE: October 20, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 29, 2025.

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

1. As development package (DP), TD-DEV-0723-00309, is still open for this site, this DP should have been submitted as a revision to TD-DEV-0723-00309. Either withdraw this DP and submit as a revision to TD-DEV-0723-00309 or complete TD-DEV-0723-00309 and then resubmit this DP

If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.
09/20/2024 CDRC Application Completeness Express REVIEW COMPLETED
09/30/2024 CDRC Review Coordinator Express REVIEW COMPLETED CDRC added TAA, ADOT, and TEP PAG, USPS, SWG to the workflow. Review request email sent to TAA, ADOT, and TEP. FYI email sent to PAG, USPS, SWG.
10/15/2024 Commercial Plumbing REVIEW COMPLETED
10/17/2024 External Reviewers - Arizona Department of Transportation (ADOT) REVIEW COMPLETED Good Afternoon,

ADOT Traffic has reviewed this DEV and has the following comments;

The future Sonoran Corridor (SR 410) will run on the northside of this Dev.
TEP is aware of this future roadway corridor and has been attending meetings for the project.

Additional information can be found online, Link to Study [azdot.gov]
https://azdot.gov/planning/transportation-studies/sonoran-corridor-sr-410-study [azdot.gov]

There does not appear to be any conflicts at this time.

Thank you for the opportunity to review this DEV.



--
Respectfully,






James Gomes, Jr., PE

SOUTHERN REGION

TRAFFIC ENGINEERING MANAGER

ARIZONA DEPARTMENT
OF TRANSPORTATION


1221 S. 2nd Ave.

Tucson, Az, 85713

520.388.4231

azdot.gov [azdot.gov]
09/30/2024 External Reviewers - Pima Association of Governments REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
09/30/2024 External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
10/18/2024 External Reviewers - Tucson Airport Authority REVIEW COMPLETED October 18, 2024
Planning and Development Services
City of Tucson
201 North Stone Avenue
Tucson, AZ. 85701
RE: TD-DEV-0924-00258, TEP Roadrunner Reserve 2 BESS / 10000 S Rita Rd, Tucson, AZ
85747, Received September 30, 2024
To whom this may concern,
Thank you for the opportunity to comment on TD-DEV-0924-00258, the development plan for a
new battery energy storage use at 10000 South Rita Road. This development is located in
Section 4, Township 16S, Range 15E, of the Gila and Salt River Meridian. The development site
occupies parcel numbers 305-01-005A, covers approximately 200.05 ± acres, and is zoned as
Rural Homestead Zone (RH) and Light Industrial Zone 1 (I-1). The nearest major roadway
intersection is South Rita Road and East Old Vail Connection Road, approximately 2,100 feet to
the northeast of the subject development.
This site does lie within the Tucson International Airport avigation easement requirements and
public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority approves the proposed project and is not requiring a resubmittal.
Please do not hesitate to contact me if you have any questions or concerns regarding this
comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-
573-4811.
Respectfully,
Scott Robidoux, C.M.
Manager of Planning
10/11/2024 External Reviewers - Tucson Electric Power (TEP) REVIEW COMPLETED October 10, 2024
WO#T129565
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: Roadrunner Reserve II Dev Pckge Civil Const
TD-DEV-0924-00258
Tucson Electric Power Company (TEP) has reviewed and approved the development
plan submitted 9/30/2024. There are existing facilities within the development which are
depicted upon the plan. Clearance must be maintained from the 138kv lines and
protect lines and poles in place.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Cruz Vega
(520) 349-9850
cruzvega@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
09/30/2024 External Reviewers - United States Postal Service (USPS) REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
10/11/2024 Fire New Construction REVIEW COMPLETED
09/27/2024 OK to Submit - Engineering Fast REVIEW COMPLETED
09/30/2024 OK to Submit - Zoning Fast REVIEW COMPLETED
10/01/2024 ROW Engineering Review REVIEW COMPLETED DTM has no comments.