Permit Number: TD-DEV-0624-00169
Parcel: 127090180

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW REVISION v.2

Permit Number - TD-DEV-0624-00169
Review Name: DEVELOPMENT PACKAGE NEW REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2025 Commercial Plumbing APPROVED
02/19/2025 CDRC Post Review Express PENDING ASSIGNMENT
02/19/2025 Site Engineering REQUIRES RESUBMIT TD-DEV-0624-00169
6105 E BROADWAY BL

Site Engineering comments are as follows:
1. The waste enclosure interior slab shall slope toward the front at 1%. See TSM 8-01.9.0 Fig-3B for single container enclosure specifications.
2. The proposed slope of the southernmost accessible ramp on Sheet C2.0 is shown to be 8.4%. Please revise to 8.3% or less. ADA Accessibility Std. §405.2
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
02/19/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: McDonald’s Rebuild - 6105 E. Broadway Blvd.
Development Package (1st Revision, 2nd Review)
TD-DEV-0624-00169

TRANSMITTAL DATE: February 19, 2025

DUE DATE: February 18, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 19, 2025.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

1. This comment was not addressed correctly. Per UDC Article 7.4.6.D.2.b a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height and you are proposing a 8” high curb. COMMENT: 2-06.4.9.H.5.a – Based on the handrails called out under Keynote 27 clearly demonstrate that the requirements of UDC Article 7.4.6.D.2.b are met.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.