Permit Number: TD-DEV-0525-00132
Parcel: 141019160

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.1

Permit Number - TD-DEV-0525-00132
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2025 Commercial Plumbing Standard APPROVED
06/03/2025 Entitlements Standard APPROVED
05/28/2025 External Reviewers - Tucson Electric Power (TEP) Standard APPROVED 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
May 28, 2025
WO#T150666
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: 5655 East 29th st
TD-DEV-0425-00125
Tucson Electric Power Company (TEP) has reviewed and Approved the development
plan submitted 5/1/2025. There are existing facilities within the development, which are
depicted upon the plan.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Martin Rodriguez
(520) 991-5495
mrodriguez@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
06/11/2025 NPPO Standard APPROVED See Site Landscape comments for possible additional notes to be added to the landscape plans with regard to the previously completed NPPO for this PAD.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
06/16/2025 Site Engineering Standard REQUIRES RESUBMIT 1. The trash enclosures proposed do not match the standard trash enclosure details found in Technical Standards Manual section 8-01. Revise as needed or get approval from Environmental Services through a Technical Standards Modification Request (TSMR).
2. Show on the plans the required 14’x40’ clear space in front of each trash enclosure per TSM Section 8-01.
3. Show the onsite maneuverability for the trash service vehicle on the plans.
4. Show how the site is compliant with the first flush retention requirements.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
06/11/2025 Site Landscape Standard REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: NEW MCDONALD'S SITE AND BUILDING
ACTIVITY NO: TD-DEV-0525-00132
PARCEL: 141019160
ZONING: PAD-12 (CIVANO PAD)
LAND USE: RESTAURANT

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape and NPPO Section review comments have been addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Per the site parking lot landscape memorandum provided by Mary Estes, PLA with Norris Design dated 05/09/25 to offset the shade tree requirement within the parking area due to the 20’ utility easement is acceptable and approved.

2. Can a reference to the Pavilions PAD Native Plant Preservation Plan and the 30% set aside be added to the cover sheet of the landscape plans or to the planting plan?

3. Provide the development package case number, TD-DEV-0525-00132, adjacent to the title block on all site landscape sheets, per Administrative Manual 2-06.4.3

4. Prior to Site Landscape Development Package approval, ensure Site Zoning and Site Engineering comments are addressed.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
520.837.4923
06/10/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: McDonald - Civano
Development Package (1st Review)
TD-DEV-0525-00132

TRANSMITTAL DATE: June 10, 2025

DUE DATE: June 6, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Per UDC Article 3.3.3.G.5.c, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 4, 2026.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

2-06.4.0 CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.3 – Provide the development package case number, TD-DEV-0525-00132, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. COMMENT: 2-06.4.7.A.4 – Remove the reference to “4.9.4.M.1 & 5 AND 4.9.13.O” from General Note 4 as PAD-12 section states “No development designators shall apply because pertinent development standards are more specifically addressed in Section E-4 of this document”.

4. COMMENT: 2-06.4.7.A.6.a - As Houghton Rd. is designated as an Arterial on the COT MS&R Map add the following to General Note 11 “UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R)”.

5. COMMENT: 2-06.4.7.A.6.a – Show the 200’ Scenic Corridor Zone on the plan, PAD-12 Section E-5.a.4) page 125.

6. COMMENT: 2-06.4.7.A.6.a – Clearly demonstrate how the requirements of PAD—12.E-5.a, page 125 & UDC Article 5.3.6.B, reference LUC Section 2.8.2.6.B.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

7. COMMENT: 2-06.4.8.B – Provide the recordation information for all existing easements shown on the plan.

8. COMMENT: 2-06.4.8.C – Provide the pavement width for Houghton Rd.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

9. COMMENT: 2-06.4.9.H.5 – Clearly demonstrate that the proposed parking canopy called out under Keynote 45 sheet SP-1, meets the requirements of UDC Article 7.4.6.F.2.A.(1) are met.

10. COMMENT: 2-06.4.9.H.5.a – Sheet C000 provide an EV parking space calculation the provides the number required and provided.

11. COMMENT: 2-06.4.9.H.5.a – Detail 4 sheet SD-1 revised the sign mounting height to read 60” when wall mounted or 84” when located within a pedestrian circulation path.

12. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculations shown on sheet C000 & SP1 do not match. The parking calculation on sheet SP1 references the LUC which is no longer applicable. Zoning recommends that you only provide a one set of required calculations for the entire set of plans on the cover sheet.

13. COMMENT: 2-06.4.9.H.5.d – Detail 10 sheet SD-1 remove the reference to “CLASS 1” from the detail as Class 1 is no longer applicable.

14. COMMENT: 2-06.4.9.L – All proposed easements will need to be recorded prior to approval of this DP.

15. COMMENT: 2-06.4.9.Q – The 36’ Max building height listed und Calculations (McDonald’s Only) sheet C000 and the allowed 30’ building height listed und Building Data, sheet SP1 are not correct This site is located within Sub-District B, Figure 29 page 126, per PAD-12 Table 8, page 121 and the allowed height is 48’.

16. COMMENT: 2-06.4.9.Q – Provide the proposed building height and specific use within the footprint of the building.

17. COMMENT: 2-06.4.9.R – Provide width dimensions for all proposed sidewalks and stripped pedestrian ways shown on the plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised development package as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf.
05/09/2025 CDRC Application Completeness Express REVIEW COMPLETED
05/15/2025 CDRC Review Coordinator Express REVIEW COMPLETED CDRC added addressing , TEP, PAG, USPS, and SWG to the workflow. Review request email sent to addressing, and TEP. FYI email sent to PAG, USPS, SWG. Also added parks and rec and entitlements.
05/16/2025 External Reviewers - COT Parks & Recreation Standard REVIEW COMPLETED Approved



Regarding TD-DEV-0525-00132, the City of Tucson Parks and Recreation Department has no additional requirements for the Development Plan and no further reviews by TPRD are required.



Description: New McDonald's Site and Building



Parcel: 141019160



Regards,



Joe Barr

Project Manager

Tucson Parks and Recreation
05/15/2025 External Reviewers - Pima Association of Governments Standard REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
06/16/2025 External Reviewers - Pima County Addressing Standard REVIEW COMPLETED Good morning,



Pima County Addressing approves TD-DEV-0525-00132.



Nicholas Jordan

Site Review Project Manager II – Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor

Tucson, AZ 85701

(520) 724-9623
05/15/2025 External Reviewers - Southwest Gas Standard REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
05/15/2025 External Reviewers - United States Postal Service (USPS) Standard REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
05/28/2025 Fire New Construction Standard REVIEW COMPLETED The following comments apply to the proposed project accordingly with the Adopted 2024 International Fire Code and Local Amendments:
1. Fire alarm and fire Sprinkler's requires a separate permit
2. Kitchen hood fire suppression systems requires a separate permit
3. CO2 systems requires an operational permit from TFD
4. A Knox type box is required at the fire riser room area.
sal.erivezjr@tucsonaz.gov
05/14/2025 OK to Submit - Engineering Fast REVIEW COMPLETED
05/15/2025 OK to Submit - Zoning Fast REVIEW COMPLETED
05/27/2025 ROW Engineering Review Standard REVIEW COMPLETED