Permit Number: TD-DEV-0523-00249
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.3

Permit Number - TD-DEV-0523-00249
Review Name: DEVELOPMENT PACKAGE NEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2023 CDRC Post Review Express PENDING ASSIGNMENT
11/14/2023 Commercial Plumbing REQUIRES RESUBMIT The revised 6” sewer now has a section that is 106 feet long and a second section that is 163 feet long. Cleanouts shall be located at intervals of not more than 100-feet of developed pipe length: additional cleanouts are needed. [Second comment: The 6” sewer being replaced requires cleanout locations to be identified (CA5.2).] [Initial comment: Building sewers smaller than 8-inches shall have cleanouts located at intervals of not more than 100-feet of developed pipe length. Reference: Section 708.1.2, IPC 2018.]
11/14/2023 CDRC Application Completeness Express REVIEW COMPLETED