Permit Number: TD-DEV-0423-00204
Parcel: 141113710

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - TD-DEV-0423-00204
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2023 CDRC Post Review Express PENDING ASSIGNMENT
05/18/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. With a cleanout rim elevation of 23.4’ and an invert of 19.9’, the maximum horizontal length between cleanouts is 96.5’. Reference: Section 708.1.1, IPC 2018.
2. Verify that Tucson Water will allow a 1” meter to be connected to a ¾” split service. Reference: Section 107.2.1, IBC 2018.
05/25/2023 NPPO REQUIRES RESUBMIT See landscape, engineering and zoning comments.
05/24/2023 ROW Engineering Review REQUIRES RESUBMIT TD-DEV-0223-00204
8219 S. Camino De Café

Comments:
1. Entrance tie-in to ROW must have a P.A.G. standard 206 Concrete Driveway Apron.
2. Where adjoining sidewalk from the property ties to sidewalk along the ROW frontage (Site Keynote No. 4,) a 60” X 60” ADA landing is required. Landings shall be 60” X 60” and not to exceed a 2% cross slope in all directions.

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov
05/15/2023 Site Engineering REQUIRES RESUBMIT 1. Show how 6" of proposed retention depth is provided NOT including any groundcover (for example, with 2" of DG, 8" of total basin depth is required
2. Show site visibility triangles (TSM 10-01.5.1)
3. Add to the ramp keynote the ADA requirement for 8.33% max running slope

Scott Haseman
scott.haseman@tucsonaz.gov
05/03/2023 Site Landscape REQUIRES RESUBMIT PROJECT: BROWN/RITA RANCH - LOT 8
ACTIVITY NO. TD-DEV-0423-00204
ADDRESS/PARCEL: 8219 S CAMINO DE CAFÉ/141-11-3710
ZONING: I-1

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all Landscape/NPPO Review Section comments are addressed.

COMMENTS:
1. Ensure that Zoning, Engineering comments and concerns are addressed prior to landscape section approval.
2. Provide the development package case number, TD-DEV-0423-00204, adjacent to the title block on all sheets. 2-06.4.3
3. You must have a permit from Department of Transit and Mobility for any planting being done in the right of way. Please reach out to David Marhefka (david.marhefka@tucsonaz.gov) if this is the case.
4. Label sight visibility triangles and ROWs (existing and future) to all landscape plans.
5. A separate irrigation water meter is required. Please label the new irrigation meter as “irrigation only” on both the irrigation plan as well as the utility plan. UDC Technical Standards 4-01.-.2. A.1.
6. Show all curb cuts/downspouts/splashpads on the landscape and the commercial rainwater harvesting plan.
7. If using d.g at a 2” depth, ensure the rainwater harvesting basins are 8” in depth to account for the d.g.

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov or 520-837-4988
05/08/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Brown/Rita Ranch – Lot 8
Development Package (1st Review)
TD-DIV-0423-00204

TRANSMITTAL DATE: May 08, 2023

DUE DATE: May 18, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is April 19, 2024.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, TD-DIV-0423-00204, adjacent to the title block on all sheets.

2-06.4.7.A.8 - For development package documents provide:

2. COMMENT: 2-06.4.7.A.8.a – Clarify why you show 3,200 SF within the building footprint and under the FAR calculation but you use 4,000 SF in the vehicle parking calculation.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

3. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculation appears to be incorrect. Based on the 3,200 SF shown within the building footprint and under the FAR calculation the required number should be 3. Calculations are not based on an assumed GFA.

4. COMMENT: 2-06.4.9.H.5.d – Provide a detail for the proposed long-term bicycle parking that clearly demonstrates how the requirements of UDC Article 7.4.9.D are met. Also under the long-term calculation you reference “WITHIN EACH BUILDING” but you show one (1) building on the plan.

5. COMMENT: 2-06.4.9.R – Show the required 4’ wide pedestrian refuge along the south side of the building, TSM Section 7-01.4.1.H.

If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/24/2023 Traffic Engineering Review REQUIRES RESUBMIT TD-DEV-0223-00204
8219 S. Camino De Café

Comments:
1. Entrance tie-in to ROW must have a P.A.G. standard 206 Concrete Driveway Apron.
2. Where adjoining sidewalk from the property ties to sidewalk along the ROW frontage (Site Keynote No. 4,) a 60” X 60” ADA landing is required. Landings shall be 60” X 60” and not to exceed a 2% cross slope in all directions.

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov
04/11/2023 CDRC Application Completeness Express REVIEW COMPLETED
04/24/2023 CDRC Review Coordinator Express REVIEW COMPLETED
04/24/2023 External Reviewers - COT Parks & Recreation REVIEW COMPLETED Hello CDRC team,
On behalf of the City of Tucson Parks and Recreation Department, I have no comments on the above development plan.

Tom Fisher
Project Manager
City of Tucson Parks and Recreation Department
900 S. Randolph Way
Tucson, Arizona 85716
(520) 837-8037
04/24/2023 External Reviewers - Pima Association of Governments REVIEW COMPLETED FYI email sent per SOP
04/24/2023 External Reviewers - Southwest Gas REVIEW COMPLETED FYI email sent per SOP
04/24/2023 External Reviewers - Tucson Electric Power (TEP) REVIEW COMPLETED FYI email sent per SOP
04/24/2023 External Reviewers - United States Postal Service (USPS) REVIEW COMPLETED FYI email sent per SOP
04/24/2023 Fire New Construction REVIEW COMPLETED
04/12/2023 OK to Submit - Engineering Fast REVIEW COMPLETED
04/11/2023 OK to Submit - Landscape Fast REVIEW COMPLETED
04/20/2023 OK to Submit - Zoning Fast REVIEW COMPLETED