Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW v.3
Permit Number - TD-DEV-0325-00090
Review Name: DEVELOPMENT PACKAGE NEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2025 | Site Zoning Standard | APPROVED | |||
| 12/15/2025 | TSMR/PDMR - Zoning | APPROVED | |||
| 12/22/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Site Engineering Review TD-DEV-0325-00090 5950 E BROADWAY BL Summary: Change of use and added patio Site Engineering comments are as follows: 1. The Engineering TSMR review comments must be addressed before Site Engineering can approve this permit. Engineering Associate: Ryan Insalaco ryan.insalaco@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised plan set as well as an itemized comment response letter. To resubmit, visit the Tucson Development Center Online at: https://tdc-online.tucsonaz.gov/#/home The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 12/22/2025 | TSMR/PDMR - Engineering | REQUIRES RESUBMIT | Comments from Andy Vera: Plan View detail, page 3. 1. Clear gate opening at face of enclosure must be 12 ft minimum. Currently identified as 11ft. 2. Must include bollards to protect the side walls, in addition to the 3 bollards identified along the rear wall. 3. Call out dimensions between the rear bollards and front gates and side wall bollards. Must be a minimum 10ft x 10 ft clear area for the container. 4. Must identify four “1.5 “ steep pipe cast into concrete paving”, for anchoring gates in the open position during service operation and when closed. Depict and annotate in Plan View detail, page 3. 5. Page 2, Noted Site Plan, identifies two double container enclosures, however, Plan View detail on page 3 presents design as single container enclosures. Detail drawing must match site plan. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |