12/18/2025 Site Zoning Standard APPROVED
12/15/2025 TSMR/PDMR - Zoning APPROVED
12/22/2025 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TD-DEV-0325-00090
5950 E BROADWAY BL
Summary: Change of use and added patio

Site Engineering comments are as follows:

1. The Engineering TSMR review comments must be addressed before Site Engineering can approve this permit.

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised plan set as well as an itemized comment response letter.

To resubmit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
12/22/2025 TSMR/PDMR - Engineering REQUIRES RESUBMIT Comments from Andy Vera:
Plan View detail, page 3.
1. Clear gate opening at face of enclosure must be 12 ft minimum. Currently identified as 11ft.
2. Must include bollards to protect the side walls, in addition to the 3 bollards identified along the rear wall.
3. Call out dimensions between the rear bollards and front gates and side wall bollards. Must be a minimum 10ft x 10 ft clear area for the container.
4. Must identify four “1.5 “ steep pipe cast into concrete paving”, for anchoring gates in the open position during service operation and when closed. Depict and annotate in Plan View detail, page 3.
5. Page 2, Noted Site Plan, identifies two double container enclosures, however, Plan View detail on page 3 presents design as single container enclosures. Detail drawing must match site plan.