Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TD-DEV-0325-00075
Parcel: 14048003A

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE NEW v.3

Permit Number - TD-DEV-0325-00075
Review Name: DEVELOPMENT PACKAGE NEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TD-DEV-0325-00075
ADDRESS/PARCEL: 8650 S ALVERNON WY TUCSON, AZ 85756

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. The maximum demand flow that is allowed by Tucson Water for the specified water meter (3/4”) is 30 GPM. A 1” water meter will be required for a flow rate demand of 43 GPM.
2. Please clarify how sanitary waste is proposed to be disposed of, as no existing or proposed sewer connection is shown on the plans. Reference Section 107.2.1, IBC 2018.
02/06/2026 External Reviewers - Tucson Airport Authority Standard REVIEW COMPLETED February 6, 2026
Planning and Development Services
City of Tucson
201 North Stone Avenue
Tucson, AZ. 85701
RE: TD-DEV-0325-00075, 3
rd Submittal, Two new concrete test pad areas for Raytheon,
Received January 14, 2026
To whom this may concern,
Thank you for the opportunity to comment on TD-DEV-0325-00075, 3
rd Submittal, the
development plan for a new concrete test pad at Tucson International Airport. This
development is located in the N.E. quarter of the S.E. quarter of Section 28, Township 15S,
Range 14E, of the Gila and Salt River Meridian. The development site occupies parcel numbers
140-48-003A, covers approximately 5.0 ± acres, and is zoned as Heavy Industrial Zone (I-2).
The nearest major roadway intersection is Aeronautical Way and South Alvernon Way,
approximately 900 feet to the northeast of the subject development.
This site does lie within the Tucson International Airport avigation easement requirements and
public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority is satisfied with the 3rd submittal of this project and requests to be
included on subsequent submittals of this project.
Please do not hesitate to contact me if you have any questions or concerns regarding this
comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-
573-4811.
Respectfully,
Scott Robidoux, C.M.
Manager of Planning
cc file