Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW v.1
Permit Number - TD-DEV-0125-00006
Review Name: DEVELOPMENT PACKAGE NEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2025 | Commercial Plumbing Standard | APPROVED | |||
| 02/26/2025 | NPPO Standard | NOT REQUIRED | A native plant preservation plan was completed on the entire 118-acre project in 2005. | ||
| 03/12/2025 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
| 03/12/2025 | Entitlements Standard | REQUIRES RESUBMIT | Per PAD-38 Section 3.C.14, a letter of approval from the established Architectural Review Committee for The Property is required. The ARC reviews and approved architectural design within the Property for compliance with the Development Standards in Section 3 of the PAD, and any additional design criteria for the Property. | ||
| 02/20/2025 | Site Engineering Standard | REQUIRES RESUBMIT | 1. Block M just south of the site is mislabeled, it should be Block N. 2. Both Blocks L and N are private and not public as noted on the plans, revise as needed. 3. S19-016 is shown on the plans as the related final plat, S19-016 was withdrawn, the correct final plat number that should be referenced is TD-DIV-1122-00011, revise as needed. 4. The directional arrows on the north side of the building are indicating two directional flow right before the exit of the one-way drive, revise as needed to ensure safe onsite maneuverability that prevents people from driving through the one way drive in reverse direction. 5. The stacking area for vehicles to be serviced appears to overlap the 14 x 40 clear space in front of the trash enclosures. Have ES review the proposed plan for approval. 6. Show a complete pedestrian circulation path throughout the site including to the trash enclosure, frontage road, and neighboring developments. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
||
| 02/26/2025 | Site Landscape Standard | REQUIRES RESUBMIT | CDRC TRANSMITTAL PLANNING AND DEVELOPMENT SERVICES DEPARTMENT REVIEWER: CHAD KELLER, RLA SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION PROJECT: PAD-36 HOUGHTON TOWN CENTER PAD - NEW VALVOLINE - MINOR AUTO SERVICE BUILDING ACTIVITY NO: TD-DEV-0125-00006 ADDRESS: 10096 E OLD VAIL RD ZONING: PAD-36 This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting. Please resubmit revised drawings along with a detailed response letter, which states how all of the Site Landscape/NPPO Section review comments have been addressed. SITE LANDSCAPE/NPPO SECTION COMMENTS: 1. Commercial Rainwater Harvesting is required for this site per the PAD 36 document, and it is stated on the plans, (sheet L01). Can a water budget table be added along with the separate rainwater harvesting plan? This will complete the landscape set. 2. It is recognized that utility easements run through some of the landscape areas that are not depressed. Can the other landscape areas be depressed 6” to catch at a minimum rainfall only (northwest landscape planting area)? Add a callout at the planting area to see detail G on sheet L03 Depressed Landscape Area. If there is a specific reason for this landscape planting area to not be depressed, please outline the reason(s). 3. PAD-36 states that UDC 7.6 landscape and screening apply. Add the street landscape border tree requirement calculation on the planting plan. 4. A couple of the plant species are not on the approved landscape plant palette per the PAD-36 document. Update plant list to include plants from the list. (Aloe and Lantana variety) 5. Should additional ¾” pvc irrigation lines and end flush caps be added schematically to the northeast and southeast large planting areas so that the distribution tubing doesn’t have to stretch so far from the emitter? (I measured approximately 50’ from the pvc lateral to the approximate location of the furthest plant in the northeast planting area.) 6. Update the line type for the pvc lateral on the plan to match the line on the legend or the other way around. 7. Will the plants proposed on the north property need to be irrigated? If so, add the shrub irrigation line and a sleeve across the access lane. 8. Call out all property lines on all plans in the landscape set. 9. Call out the proposed ROW on the landscape sheets. 10. On the cover sheet, update the sheet index number10 to read irrigation plan. 11. Provide the development package case number, TD-DEV-0125-00006, adjacent to the title block on all sheets. 2-06.4.3 Thank you. Chad Keller, RLA Landscape Architect chad.keller@tucsonaz.gov 520.837.4923 |
||
| 02/18/2025 | Site Zoning Standard | REQUIRES RESUBMIT | CDRC TRANSMITTAL FROM: Bobby Parsons PDSD Zoning Review Section PROJECT: 10096 E Old Vail Rd Tucson, AZ 85747 Development Package (1st Review) TD-DEV-0125-00006 TRANSMITTAL DATE: 2/18/2025 DUE DATE: 2/18/2025 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 9, 2026. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) CONTENT REQUIREMENTS 2-06.4.2 - The title block shall include the following information and be provided on each sheet: 2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat; 1. COMMENT: 2-06.4.2.B – Please include “HOUGHTON TOWN CENTER SQ20231170380 LOT 41” in the legal description. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 2. COMMENT: 2-06.4.3 - Provide the development package case number, TD-DEV-0125-00006, adjacent to the title block on each sheet. 2-06.4.6 - If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the PAD on the first sheet, indicating the location of the portion being developed. 3. COMMENT: 2-06.4.6 – Please provide the drawing as noted by the standard above (PAD 36). 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. Zoning and Land Use Notes 2-06.4.7.A.8 - For development package documents provide: 2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage; 4. COMMENT: 2-06.4.7.A.8.b – Per Table C.1.0 Development Standards in the PAD 36 document, the maximum floor area ratio allowed is 20% for HTC1 and HTC2 combined. Please include this calculation in the general notes. 2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met. 5. COMMENT: 2-06.4.7.A.8.d – Please include an updated zoning table calculations as depicted on DP18-0081 to include this new development. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system. 6. COMMENT: 2-06.4.8.A – Per the approved final plat, the provided property dimensions are not consistent with the approved lot dimensions. Please clarify the discrepancy. 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. 7. COMMENT: 2-06.4.8.B – The 15’ TEP electrical easement does not appear to continue as noted on your plans. Please provide documentation that this easement extends as shown on page 5. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 8. COMMENT: 2-06.4.8.C – According to the approved plat, Block L is a private road and Block M is mislabled as it should read Block N (Private). Please update accordingly. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements. 9. COMMENT: 2-06.4.9.A – Per the approved final plat, the provided property dimensions are not consistent with the approved lot dimensions. Please clarify the discrepancy as noted in standard 2-06.4.8.A. 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. 10. COMMENT: 2-06.4.9.H.4 – Block L and Block N need to be labeled as “Private”. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 11. COMMENT: 2-06.4.9.H.5 – Keynote 19 on the site plan indicates directional arrows however to the east of the building it is one way. Please clarify as the arrows to the north of the building appear to send traffic towards the one way drive lane. If this is a one way drive only, please update the keynote. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 12. COMMENT: 2-06.4.9.H.5.a – Please delineate the parking spaces overhang adjacent to all sidewalks and landscape areas. Please provide a dimensioned detail drawing of the ADA parking space and access aisle. If the sidewalk is raised in front of the ADA parking space, please add dimensioned detail for the access ramp. If the sidewalk is flush with the access isle, please add a note stating so. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. 13. COMMENT: 2-06.4.9.R – Please clarify how pedestrian circulation will interconnect with the rest of the development. 2-06.4.9.S - Show existing or proposed pedestrian circulation along abutting rights-of-way. Such sidewalks must comply with accessibility requirements for the physically disabled and the design criteria in Section 10-01.0.0, Street Technical Standards, of the Technical Standards Manual. 14. COMMENT: 2-06.4.9.S – Please clarify why there is no sidewalks fronting the site. 2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm. 15. COMMENT: 2-06.4.9.T – Please demonstrate pedestrian circulation to the dumpster location. ***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations If you have any questions about this transmittal, Contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and comment response letter. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home. Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf. |
||
| 01/15/2025 | CDRC Application Completeness Express | REVIEW COMPLETED | |||
| 01/27/2025 | CDRC Review Coordinator Express | REVIEW COMPLETED | CDRC added Parks Rec, Entitlements and TEP PAG, USPS, SWG to the workflow. Review request email sent to Parks Rec, Entitlements and TEP. FYI email sent to PAG, USPS, SWG. | ||
| 03/10/2025 | External Reviewers - COT Parks & Recreation Standard | REVIEW COMPLETED | he City of Tucson Parks and Recreation Department has no additional requirements for the Development Plan for TD-DEV-0125-00006 and no further reviews by TPRD are required. | ||
| 01/27/2025 | External Reviewers - Pima Association of Governments Standard | REVIEW COMPLETED | Sent FYI email per SOP. | ||
| 01/27/2025 | External Reviewers - Southwest Gas Standard | REVIEW COMPLETED | Sent FYI email per SOP. | ||
| 02/21/2025 | External Reviewers - Tucson Electric Power (TEP) Standard | REVIEW COMPLETED | February 20, 2025 WO#T140923 City of Tucson Planning and Development Services Attn: CDRC Admin Team Dear CDRC Admin Team Subject: Valvoline TD-DEV-0125-00006 Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted 1/28/2025. There is an existing primary line on site that may conflict. This line should be protected in place. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. To apply for electric service, please call the New Construction department at (520) 918- 8300. Please submit a final set of plans including approved site, electric load, paving off-site improvements and irrigation plans. If available, include a PDF version of the plans. If easements are required, they will be secured by separate instrument. Should you have any easement questions, please contact our Land Resources Department, LandReviews@tep.com. Should you have any technical questions, please contact the area designer, Cruz Vega (520) 349-9850 cruzvega@tep.com Sincerely, Design Admins Design Admins Tucson Electric Power |
||
| 01/27/2025 | External Reviewers - United States Postal Service (USPS) Standard | REVIEW COMPLETED | Sent FYI email per SOP. | ||
| 01/27/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 01/23/2025 | OK to Submit - Engineering Fast | REVIEW COMPLETED | |||
| 01/22/2025 | OK to Submit - Zoning Fast | REVIEW COMPLETED | |||
| 01/27/2025 | ROW Engineering Review Standard | REVIEW COMPLETED | DTM has no comments. |